VC Pro VRF 50/60Hz
16
Midea VC Pro Series Engineering Data Book
Table 1-6.5: Extract from Table 1-5.2 Combinations of Indoor and outdoor units
Sum of capacity indexes of
connected indoor units (standard
indoor units only)
Maximum number of
connected indoor
units
The number of connected indoor units is 8 and the maximum number of connected indoor units on the 20HP outdoor
unit is 33, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor units:
a) The sum of the indoor unit CIs is 706 and the CI of the 20HP outdoor unit (MVC-560WV2GN1) is 560, so the
combination ratio is 706 / 560 = 126%.
b) Using the outdoor units’ cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-6.6 and 1-6.7.
Table 1-6.6: Extract from Table 2-8.7 MVC-560WV2GN1
cooling capacity
Table 1-6.7: Cooling capacity calculated by
interpolation
Outdoor
air
temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
Outdoor
air
temp.
(°C DB)
Indoor air temp.
(°C DB / °C WB)
Notes:
1. 59.32 + (60.37 – 59.32) × (126 – 120) / (130 – 120) =
59.95