The number of connected indoor units is 4 and the maximum number of connected indoor units on the 120 model
outdoor unit is 8, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor unit:
a) The sum of the indoor unit CIs is 120 and the CI of the 120 model outdoor unit is 123, so the combination ratio is
120 / 123 = 97.5%.
b) Using the outdoor unit’s cooling capacity table, interpolate to obtain the capacity (“B”) corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.6 and 1-5.7.