TROUBLESHOOTING
8
8-1. HOW TO CHECK THE PARTS
PKFY-P06NBMU-E PKFY-P08NBMU-E
PKFY-P06NBMU-ER1 PKFY-P08NBMU-ER1
Parts name Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 50°F~86°F)
Disconnect the connector then measure the resistance value with a tester.
(Coil temperature 68°F)
Linear expansion
valve (LEV)
Refer to the next page for the details.
Room temperature
thermistor (TH21)
Liquid pipe temperature
thermistor (TH22)
Gas
pipe temperature
thermistor (TH23)
Normal
4.3k~9.6k
Abnormal
Open or short
Normal
200 ± 10%
Abnormal
(1)-(5)
White-Red
(2)-(6)
Yellow-Brown
(3)-(5)
Orange-Red
(4)-(6)
Blue-Brown
Open or short
1
2
3
4
5
6
LEV
White
Yellow
Orange
Blue
Red
Brown
CN60
Vane motor (MV)
Measure the resistance between the terminals with a tester. (At the ambient temperature 77°F)
Normal Normal
400 ± 7%
Abnormal
-
Red-White
-
Red-Blue
-
Red-Orange
-
Red-Yellow
Open or short
Measure the resistance between the terminals with a tester. (At the ambient temperature 68°F)
Fan motor (MF)
Abnormal
Open or short
White-Black
Red-Black
Normal
313 ± 8%
108 ± 8%
Orange
White
Red
Yellow
Blue
4
2
1
53
Connect pin No.
M
White
Red
Black
1
4
6
FAN
OCH461B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Electric City Multi PKFY Series and is the answer not in the manual?

Mitsubishi Electric City Multi PKFY Series Specifications

General IconGeneral
BrandMitsubishi Electric
ModelCity Multi PKFY Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals