PEAD-RP(M)JAA - PEA-RP(M)GAA-WJA and SEZ-KD
Static Pressure Matrix
PAR-31(2)MAA
Static Pressure settings are different from model to model.
To increase or decrease the static pressure follow the steps outlined below;
1. Turn the controller OFF.
2. Select Menu using button.
3. Select Service using the down curser key (F1)
4. Enter Maintenance password default 9999 using (F1, F2, F3, F4 keys)
5. Press key to acknowledge.
6. Select Function setting using (F1 and F2) Keys
7. Press key to acknowledge
8. Select Ref. address of the unit to be changed (F1 and F2)
Select All for the refrigerant group using (F3 and F4)