71
-
'13 • PAC-DB-194
10.2 Correction of cooling and heating capacity in relation to air flow rate control
(fan speed)
10.3 Correction of cooling and heating capacity in relation to one way length of
refrigerant piping
It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor
and outdoor units.
Note (1) SRK series only.
Cooling 1.00 0.95
Fan speed
Coefficient
HiP-Hi or Hi
(1)
0.93 0.90
Heating 1.00 0.97 0.96 0.94
LoMe
30
0.92
15 20 25
0.97 0.96 0.94
7.5 10
1
1
0.99
1 1 11 1
Equivalent piping length (m)
Cooling
Heating
Piping length limitations
Model
Item
FDT, FDEN, FDU, FDUM, SRK
Max. one way piping length
30m
FDF
23m
Max. vertical height difference
Outdoor unit is higher 20m
Outdoor unit is lower 20m
Note (1) Values in the table indicate the one way piping length between the indoor and outdoor units.
How to obtain the cooling and heating capacity
Net cooling capacity = 9.0 × 1.00 × 0.97 × 0.99
8.6kW
Example : The net cooling cap acity of the model FDT90VNPVF 1 with the air flow P-High”, the piping length of 15m, the outdoor
unit located 5m lower than the indoor unit, indoor wet-bulb temperature at 19.0and outdoor dry-bulb temperature 35 is
Net cooling total capacity
of FDT90VNPVF1
(Outdoor temp. : 35DB
Indoor temp. : 19WB)
shown in table 10.1
Air flow : P-High
shown in table 10.2
Piping length : 15m
(Gas pipe size is φ15.88)
shown in table 10.3
Height diff. : 5m
(Outdoor unit : below)
shown in table 10.4
5m 10m 15m 20m
0.99 098 0.97 0.96
When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in
heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table.
Height difference between the indoor unit and
outdoor unit in the vertical height difference
10.4 Height difference between the indoor unit and outdoor unit
Adjustment coefficient
.
.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT71VNPVF1 and is the answer not in the manual?

Mitsubishi Heavy Industries FDT71VNPVF1 Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT71VNPVF1
CategoryAir Conditioner
LanguageEnglish

Related product manuals