Readjusting the default settings
If the room temperature does not reach the target, readjustment
may be necessary.
Cold weather conditions
When the room temperature is too low, the “Heating curve”
value is increased in menu 2.1.2 by one increment.
When the room temperature is too high, the Heating
curve” value is decreased in menu 2.1.2 by one increment.
Warm weather conditions
If the room temperature is low, increase the “Heating curve
offset” setting by one step clockwise.
If the room temperature is high, reduce the “Heating curve
offset” setting by one step anti-clockwise.
Heating system 2
If the heating system has two different type of emitter like
radiator and under floor heating, it is possible to set two
different calculated supply temperature. System 1 for higher
supply temperature can be set in menu 2.1.0, and system 2 for
lower supply temperature can be set in menu 3.0.
Vacation set back
When you are away from home for a long time, it is possible to
set the target supply water temperature for heating lower than
usual to save energy consumption. Also, it is possible to cancel
hot water operation during the period.
For details, see menu 7.5.0 Vacation set back.
Silent mode
If you like to reduce noise from outdoor unit, it is possible to do
by reducing the compressor speed and fan speed in outdoor unit.
For details, see menu 7.6.0 Silent mode.
Comfort setting with room sensor
If MH-RG10 is installed, operation mode is chosen not only by
outdoor temperature but also by room temperature.
Upper limit of the outdoor temperature to operate in Heating
mode can be set in menu 8.2.3 Stop temp Heating.
Lower limit of the outdoor temperature to operate in Cooling
mode can be set in menu 8.2.4 Start temp Cooling.
Target room temperature can be adjusted by turning the knob
on MH-RG10, and it is displayed in menu 6.3.
For details, see instruction manual for MH-RG10. The below
gure shows an example of mode transition.
NOTE
Mode transition wouldn’t happen even if MH-RG10 is
installed in case Heating or Cooling mode is chosen.
Choose Auto or AutoC in case room sensor is used.
Stop temp
Heating (8.2.3)
Start temp
Cooling (8.2.4)
Target
room temp
(6.3)
Hot water production
Heating
Cooling
Room temperature
Mode transition (in case AutoC is chosen)
Outdoor temperature
LEK
Knob
MH-RG10
Comfort setting heating

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries HMA100V and is the answer not in the manual?

Mitsubishi Heavy Industries HMA100V Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelHMA100V
CategoryHeat Pump
LanguageEnglish

Related product manuals