EasyManuals Logo
Home>Mitsubishi>Controller>FX1N Series

Mitsubishi FX1N Series Hardware Manual

Mitsubishi FX1N Series
8 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
FX
1N
JAPANESE SPECIFICATION UNITS
HARDWARE MANUAL
JY997D07901A
This manual contains safety information, associated manual listings, specifications and terminal layouts
and wiring for Japanese specification FX
1N
PLC main units.
For complete operation, mounting and programming instructions please refer to the FX
1N
HANDY
MANUAL (JY992D87501 JAPANESE ONLY) and PROGRAMMING MANUAL.
These manuals should be read and understood before attempting to install or use the unit.
Guidelines for the Safety of the User and Protection of the FX
1N
PLC
This manual has been written to be used by trained and competent personnel. The definition of such a
person or persons is as follows:
a) Any engineer who is responsible for the planning, design and construction of automatic equipment using the
product associated with this manual, should be of a competent nature, trained and qualified to the local and
national standards. These engineers should be fully aware of all aspects of safety with regards to automated
equipment.
b) Any commissioning or service engineer must be of a competent nature, trained and qualified to the local and
national standards. These engineers should also be trained in the use and maintenance of the complete
product. This includes being completely familiar with all associated documentation for the said product. All
maintenance should be carried out in accordance with established safety practices
c) All operators of the completed equipment should be trained to use that product in a safe and co-ordinated
manner in compliance to established safety practices. The operators should also be familiar with documentation
which is connected to the actual operation of the completed equipment
Note:
The term ‘completed equipment’ refers to a third party constructed device which contains or uses
the product associated with this manual.
Note’s on the Symbols Used in this Manual
At various times through out this manual certain symbols will be used to highlight points of information
which are intended to ensure the users personal safety and protect the integrity of equipment.
1) Indicates that the identified danger could
POSSIBLY
cause physical and property damage.
2) Indicates a point of further interest or further explanation.
Under no circumstances will Mitsubishi Electric be liable or responsible for any consequential damage
that may arise as a result of the installation or use of this equipment.
All examples and diagrams shown in this manual are intended only as an aid to understanding the
text, not to guarantee operation. Mitsubishi Electric will accept no responsibility for actual use of the
productbased on these illustrative examples.
Owing to the very great variety in possible application of this equipment, you must satisfy yourself as
to its suitability for your specific application.
Further Information Manual Lists
The following manuals are recommended as essential reference material for the correct operation of an
FX
1N
series Programmable Controller
Manual name Manual No. Description
FX
1N
HANDY MANUAL
JY992D87501
(JAPANESE ONLY)
Describes contents related to hardware of world
specification FX
1N
series PLCs such as
specifications, wiring and installation.
FX
1S
, FX
1N
, FX
2N
, FX
2NC
PROGRAMMING
MANUAL
JY992D62001
(JAPANESE ONLY)
Programming manual for FX
1S
, FX
1N
, FX
2N
and
FX
2NC
series Programmable Logic Controllers
1. Introduction
This manual covers basic hardware details for the FX
1N
Series Programmable Logic Controller.
1.1 World Specification
MODEL
INPUT OUTPUT
POWER
SUPPLY
DIMENSIONS
mm (inches)
WEIGHT
kg (lbs)
QTY TYPE QTY TYPE
FX
1N
-24MR
14
(16)
24V DC
SINK
10
(16)
Relay
100-240
VAC
+10%
-15%
50/60Hz
90
(3.6)
90
(3.5)
75
(3.0)
0.45
(0.99)
FX
1N
-24MT
Transistor
FX
1N
-40MR
24 16
Relay
130
(5.2)
0.65
(1.44)
FX
1N
-40MT
Transistor
FX
1N
-60MR
36
(40)
24
Relay
175
(7.0)
0.80
(1.77)
FX
1N
-60MT
Transistor
FX
1N
-24MR-D
14
(16)
24V DC
SINK
10
(16)
Relay
12V DC
-15%
to
24V DC
+20%
90
(3.6)
90
(3.5)
75
(3.0)
0.45
(0.99)
FX
1N
-24MT-D
Transistor
FX
1N
-40MR-D
24 16
Relay
130
(5.2)
0.65
(1.44)
FX
1N
-40MT-D
Transistor
FX
1N
-60MR-D
36
(40)
24
Relay
175
(7.0)
0.80
(1.77)
FX
1N
-60MT-D
Transistor
Input - Sink/Source
World Spec models: SINK/SOURCE. Japanese models: ALWAYS SINK
Output - Transistor
World Spec models: ALWAYS SOURCE. Japanese models: ALWAYS SINK
2. Specifications
The installation of FX
1N
products has been designed to be safe and easy. When the products associated
with this manual are used as a system or individually, they must be installed in a suitable enclosure. The
enclosure should be selected and installed in accordance to the local and national standards.
Item Description
Operating Temperature 0 to 55 °C (32 to 131 °F)
Storage Temperature -20 to 70 °C (-4 to 158 °F)
Operating Humidity 35 to 85% Relative Humidity, No condensation
storage Humidity 35 to 90% Relative Humidity, No condensation
Vibration Resistance
- Direct Mounting
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.75 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Vibration Resistance
- DIN rail Mounting
Conforms to IEC 68-2-6; 10 - 57 Hz: 0.035 mm Half Amplitude
57 -150 Hz: 4.9 m/s
2
Acceleration
Sweep Count for X, Y, Z: 10 times (80 min in each direction)
Shock Resistance
Conforms to IEC 68-2-27: 147m/s
2
Acceleration, Action Time: 11ms
3 times in each direction X, Y, and Z
Noise Immunity 1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
Dielectric Withstand
Voltage
AC unit = 1500 V AC > 1 min, tested between all points, terminals and ground
DC unit = 500 V AC > 1 min, tested between all points, terminals and ground.
Insulation Resistance 5 M
> at 500 V DC, tested between all points, terminals and ground
Grounding
Grounding resistance 100
or less
Use a cable of at least 0.2mm
2
(AWG24) to ground equipment.
Note that ground cable must not be connected to the same ground as power
circuits. Grounding is recommended but if a proper ground cannot be
provided, the PLC will operate correctly without.
Item Description
2.1 Power Specifications
*1 Includes the input current (7 or 5 mA per point)
2.2 Input Specifications
AC Powered Units FX
1N
-24M FX
1N
-40M FX
1N
-60M
Power Supply 100-240V AC +10% -15%, 50-60 Hz
Max. allowable momentary power failure 10ms; If less than 10ms, PLC continues operation
Fuse (size) rating 250V 1A 250V 3.15A (3A)
In-rush current
100V AC - Max. 30A for 5ms
200V AC - Max. 50A for 5ms
Power Consumption *1 30W 32W 35W
DC Powered Units FX
1N
-24M FX
1N
-40M FX
1N
-60M
Power Supply 24V DC + 20% - 12V DC -15% (28.8 ~ 10.2 V DC)
Max. allowable momentary power failure 5ms; If less than 5ms, PLC continues operation
Fuse (size) rating 125V 3.15A (3A)
In-rush current
24V DC - Max. 25A for 1ms
12V DC - Max. 22A for 0.3ms
Power Consumption
15W 18W 20W
FX
1N
Main unit
FX
0N
, FX
2N
Extension
block
X0
!
!!
!
X7 X10
!
!!
!
Input voltage 24V DC
±
10%
Input current 24V DC, 7mA 24V DC, 5mA 24V DC, 5mA
Input switching current
OFF
!
ON >4.5mA >3.5mA >3.5mA
ON
!
OFF <1.5mA
Response time 10ms
Variable response time 0-15ms ---
Circuit isolation Photocoupler
Operation indication LED is lit
2.3 Output Specifications
Description Relay Output Transistor Output
Switched voltages (resistive load)
240V AC,
30V DC 5-30V DC
Rated current / N points
(resistive load)
2A/1 point, 8A/COM 0.5A/1 point, 0.8A/COM
Max. Inductive load 80VA, 120/240V AC 12W/24V DC
Max. lamp load (tungsten load)
100W (1.17A/85V AC, 0.4A/
250V AC)
1.5W/24V DC
Minimum load
When supply voltage < 5V
DC allow at least 2mA flow
------------------
Response
time (approx.)
OFF
!
ON
10ms < 0.2ms; < 5
µ
s (Y0,Y1 only)
ON
!
OFF
10ms < 0.2ms (I > 0.2A); <5
µ
s (Y0,Y1 only)
Circuit isolation By Relay PhotoCoupler
Open circuit current leakage ---------------- 0.1mA/30V DC
Operation indication LED is lit when coil is energized
3. Installation Notes
The installation of FX
1N
products has been designed to be safe and easy. If during the installation of these
products or associated products concern is felt, please contact a professional electrician who is trained to
the local and national standards applicable to the installation site.
FX
1N
Main PLC units can be either directly or DIN rail mounted. For details of either method, and
installation guidelines please refer to the FX
1N
HANDY MANUAL JY992D87501 (JAPANESE ONLY).
Mounting Cautions
Units should not be installed in areas subject to the following conditions: excessive or con-
ductive dust, corrosive or flammable gas, moisture or rain, excessive heat, regular impact
shocks or excessive vibration.
Take special care not to allow debris to fall inside the unit during installation e.g. cut wires,
shavings etc. Once installation is complete remove the protective paper band, to prevent
overheating.
Industrial automation
Elincom
Group
EuropeanUnion: www.elinco.eu
Russia: www.elinc.ru

Other manuals for Mitsubishi FX1N Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi FX1N Series and is the answer not in the manual?

Mitsubishi FX1N Series Specifications

General IconGeneral
BrandMitsubishi
ModelFX1N Series
CategoryController
LanguageEnglish

Related product manuals