123
-
'11 • SCM-SM-110
Error code
Remote controller:
LED Green Red
Outdoor
Content
1 time flash
Indoor
Keeps flashing
Stays OFF
E41
  
1. Applicable model
5. Troubleshooting
Model SCM100, 125 only
Diagnosis Countermeasure
YES
YES
YES
YES
Correct.
Replace the fan motor or outdoor control
PCB.
Replace the power transistor
temperature thermistor.
* Characteristics of power transistor temperature thermistor
Is the
installation space of outdoor
unit enough?
Is the outdoor fan running?
NO
Are the
characteristics of power transistor temperature
thermistor OK?
Connect.
Is the power
transistor temperature thermistor connector
connection OK?
Is it OK the fixing
to power transistor radiator fin?
Does it recur?
NO
0
20
40
60
80
100
120
140
160
180
200
0 20 40 60 80 100 120 140
Temperature (°C)
Temperature thermistor resistance (k)
NO
Temperature-resistance characteristics
NO
NO
NO
Fixed screw
Application of radiation
silicone
YES
Fix properly.
OK
2. Error detection method
Anomalous rise of the internal
power transistor temperature
3.
Condition of Error displayed
When anomalous rise of the
power transistor temperature is
detected 2 times within 1 hour.
4. Presumable cause
Defective inverter PCB
Defective outdoor fan motor
Delective power transistor
temperature thermistor
Inadequate installation space
Note:
Power transistor overheat
(Model SCM100, 125)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi SCM100ZJ-S1 and is the answer not in the manual?

Mitsubishi SCM100ZJ-S1 Specifications

General IconGeneral
BrandMitsubishi
ModelSCM100ZJ-S1
CategoryAir Conditioner
LanguageEnglish

Related product manuals