(220/240V)
Item
Model
SRK501HENF-L SRK561HENF-L
Cooling
High pressure MPa(kgf/cm
2
)
Heating 1.67~1.86 (17 ~ 19) 1.76 ~ 1.96 (18 ~ 20)
Cooling 0.39 ~ 0.49 (4 ~ 5) 0.34 ~0.44 (3.5 ~ 4.5)
Low pressure MPa(kgf/cm
2
)
Heating
Cooling 12 ~ 16 13 ~ 18
Heating 19 ~ 23 21 ~ 25
Cooling 8.4/8.2 10.2/9.53
Running current (A)
Heating 8.5/8.3 10.5/9.95
Temp. difference between
suction air and discharge air (˚C)
Note (1) The data are measured at following conditions.
Ambient air temperature
Indoor side: Cooling ... 27°C DB, 19°C WB, Heating ... 20°C DB
Outdoor side: Cooling ... 35°C DB, 24°C WB, Heating ... 7°C DB, 6°C WB
2.5.6 Precautions for wireless remote controller installation and operation
(1) Wireless remote controller covers the following distances:
(a) When operating facing the air-conditioner:
Notes (1) The remote controller is correctly facing the sensing
element of the air conditioner when being manipulated.
(2) The typical coverage is indicated (in the left
illustration). It may be more or less depending on the
installation.
(3) The coverage may be less or even nil. If the sensing
element is exposed to strong light, such as direct
sunlight, illumination, etc., or dust is deposited on it or
it is used behind a curtain, etc.
less
or
or less
6 m or less
Wireless remote
controller
6 m or less
Remote control
available in this area.
Receiver
or less
(b) When manipulating the remote controller mounted on a wall:
Make sure that it works normally (i.e., transmission/reception signal is
audible) before mounting.
(b) Cooling only type (220/240V)
Item
Model
SRK501CENF-L SRK561CENF-L
High pressure MPa(kgf/cm
2
)–
Low pressure MPa(kgf/cm
2
) 0.39 ~ 0.49 (4 ~ 5) 0.34 ~ 0.44 (3.5 ~ 4.5)
12 ~ 16 13 ~ 18
Running current (A) 8.4/8.2 10.2/9.53
Temp. difference between
suction air and discharge air (˚C)