(7) Standard operation data
(a) Heat pump type (220/240V)
Item
Model
SRK208HENF-L SRK288HENF-L SRK328HENF-L SRK408HENF-L
Cooling ––––
High pressure (kgf/cm
2
G)
Heating 15 ~ 17 17 ~ 19 17 ~ 19 18 ~ 20
Cooling 4.5 ~ 5.5 4 ~ 5 4.5 ~ 5.5 4 ~ 5
Low pressure (kgf/cm
2
G)
Heating ––––
Cooling 14 ~ 16 11 ~ 15 12 ~ 16 12 ~ 16
Heating 16 ~ 18 18 ~ 22 18 ~ 22 18 ~ 22
Cooling 3.4/3.6 4.5/4.6 6.9/6.9 6.4/6.4
Running current (A)
Heating 3.0/3.4 4.0/4.1 6.1/6.1 6.5/6.5
(220V/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side: Cooling ... 27°C DB, 19°C WB, Heating ... 20°C DB
Outdoor side: Cooling ... 35°C DB, 24°C WB, Heating ... 7°C DB, 6°C WB
Temp. difference between suction
air and discharge air (˚C)
(b) Cooling only type (220/240V)
Item
Model
SRK208CENF-L SRK258CENF-L SRK288CENF-L SRK328CENF-L SRK408HENF-L
High pressure (kgf/cm
2
G) –––––
Low pressure (kgf/cm
2
G) 5 ~ 6 5 ~ 6 4 ~ 5 5 ~ 6 4 ~ 5
11 ~13 12 ~ 16 13 ~ 17 12 ~ 16 13 ~ 17
Running current (A) 2.5/2.6 3.3/3.4 4.1/4.2 4.3/4.4 6.4/6.4
(220/240V)
Note (1) The data are measured at following conditions
Ambient air temperature
Indoor side: 27°C DB, 19°C WB
Outdoor side: 35°C DB, 24°C WB
Temp. difference between
suction air and discharge
air (˚C)