(2) Within 30 minutes after either auto or manual operation stops, if auto operation is started, or if you switch to auto operation during
manual operation, the system runs in the previous operation mode.
(3) The temperature is checked 1 time in 30 minutes after the start of operation, and if the judgment differs from the previous operation
mode, the operation mode changes.
(4) Setting temperature can be adjusted within the following range. There is the relationship as shown below between the signals of the
wireless remote control and the setting temperature.
Signals of wireless remote control (Display)
–6 –5 –4 –3 –2 –1 ±0+1+2+3+4+5+6
Setting
Cooling 18 19 20 21 22 23 24 25 26 27 28 29 30
temperature
Dehumidifying 18 19 20 21 22 23 24 25 26 27 28 29 30
Heating 20 21 22 23 24 25 26 27 28 29 30 31 32
4.12 Regulation of outdoor air flow
The fan operates as follows according to the outdoor air temperature. (Except during defrost.)
S SRK52 HE, 63 HE
Cooling, thermaldry Heating
Outdoor air temp. (˚C)
32
2nd speed
1st speed
30
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
S SRK71 HE
Cooling, thermaldry Heating
Outdoor air temp. (˚C)
25
2nd speed
1st speed
23
3rd speed
3230
Outdoor air temp. (˚C)
12
2nd speed
1st speed
10
3rd speed
1816