NAPCO StarLink Fire: Getting Started Guide 27
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2017
The NAPCO SLECDMAI-CFB-PS and SLE3/4GI-CFB-PS Commercial Fire communicators, fully compliant with the
2013 edition of NFPA 72, are approved as Dual Path fire alarm communicators. The capability of indicating and communi-
cating signal failures to the central station within 6 hours of an outage allows the SLECDMAI-CFB-PS or SLE3/4GI-CFB-PS
to replace two existing telephone lines. Note: The SLECDMAI-CFB-PS and SLE3/4GI-CFB-PS may also be configured
as Sole Path Fire communicators, fully compliant with the NFPA 72, 2013 edition.
The following testing guide is intended to assist with the AHJ inspection of a SLECDMAI-CFB-PS or SLE3/4GI-CFB-PS
Fire radio installation. All required testing procedures are described, followed by the correct system responses. Ensure that
in cases where a radio trouble output is connected to an input on the FACP, the fire control panel properly annunciates the
trouble condition.
Normal LED Indications
With the SLECDMAI-CFB-PS or SLE3/4GI-CFB-PS in standby mode, ensure the LEDs display as follows:
AC Failure Test
Remove radio AC power and observe the following SLEULPS-R power supply indications:
Restore radio AC power:
No Battery / Low Battery Test
Disconnect the radio battery and observe the following SLEULPS-R power supply indications:
(continued)
StarLink
™
SLECDMAI-CFB-PS & SLE3/4GI-CFB-PS
Dual Path Fire Communicator
NFPA 2013 AHJ Inspection Guide
WI2261LF 9/17
LED on SLEULPS-R Verify this Condition Passed?
Yellow Trouble LED Blinks once.
Trouble Relay Output Activates after 2 hours; check for proper trouble annunciation at FACP.
Yellow Trouble LED Turns off.
Trouble Relay Output Restores; check for proper trouble restoral at FACP.
LED on SLEULPS-R Verify this Condition Passed?
Yellow Trouble LED Blinks twice.
Trouble Relay Output
Activates within 200 seconds; check for proper trouble annunciation at
FACP
LED Verify this Condition Passed?
Yellow Operational LED DS15 1 Slow Blink (indicates normal operation).
Green IP Network LED DS14 1 Blink (Static IP) or 2 Blinks (DHCP).
Red IP Trouble LED DS16 OFF (indicates no trouble present).
Yellow Operational LED D4 Blinks every 10 seconds (indicates normal operation).
Green RF Signal LED D3 Blinks at least 4 times (indicates minimally acceptable signal strength).
Red Trouble LED D5 OFF (indicates no trouble present).
Trouble Relay Output on
SLEULPS-R Trouble LED
OFF (indicates no trouble present).