NAPCO StarLink Fire: Getting Started Guide 31
The NAPCO SLE-CDMAI-FIRE / SLE-GSMI-FIRE and SLECDMAI-CFB / SLE3/4GI-CFB Commercial Fire communica-
tors, fully compliant with the 2010 edition of NFPA 72, are approved as Dual Path fire alarm communicators. The capability
of indicating and communicating signal failures to the central station within 24 hours of an outage allows each unit to replace
two existing telephone lines. Note: The SLE-CDMAI-FIRE / SLE-GSMI-FIRE and SLECDMAI-CFB / SLE3/4GI-CFB may
also be configured as Sole Path Fire communicators, fully compliant with the NFPA 72, 2010 edition.
The following testing guide is intended to assist with the AHJ inspection of a SLE-CDMAI-FIRE / SLE-GSMI-FIRE or SLEC-
DMAI-CFB / SLE3/4GI-CFB Fire radio installation. All required testing procedures are described, followed by the
correct system responses. Ensure that in cases where a radio trouble output is connected to an input on the FACP, the fire
control panel properly annunciates the trouble condition.
Normal LED Indications
With the unit in standby mode, ensure the LEDs display as follows:
AC Failure Test
No Battery / Low Battery Test
The SLE-CDMAI-FIRE / SLE-GSMI-FIRE and SLECDMAI-CFB / SLE3/4GI-CFB models are powered directly from
the FACP power supply; radio AC Failure and Battery Failure tests are not required.
Signal Loss Test
This test ensures that the SLE-CDMAI-FIRE / SLE-GSMI-FIRE or SLECDMAI-CFB / SLE3/4GI-CFB will indicate a
supervisory trouble condition to the FACP and central station upon loss of signal within the required time.
Remove the antenna and observe the following indications:
(continued)
333 Bayview Avenue, Amityville, New York 11701
For Sales and Repairs, (800) 645-9445
For Technical Service, (800) 645-9440 or visit us at
http://tech.napcosecurity.com/
(Note: Technical Service is for security professionals only)
Publicly traded on NASDAQ Symbol: NSSC
© NAPCO 2017
WI2262LF 9/17
StarLink
SLE-CDMAI-FIRE / SLE-GSMI-FIRE
& SLECDMAI-CFB / SLE3/4GI-CFB
Dual Path Fire Communicators
NFPA 2010 AHJ Inspection Guide
LED Verify this Condition Passed?
Red Trouble LED D5 Blinks 5 times.
Trouble Relay Output on
PGM1 Trouble Output
Activates within 24 hours; check for proper trouble annunciation at
FACP
Supervisory signal E788 (zone 1) will be received by the central station
within 24 hours of the antenna being removed.
LED Verify this Condition Passed?
Yellow Operational LED DS15 1 Slow Blink (indicates normal operation).
Green IP Network LED DS14 1 Blink (Static IP) or 2 Blinks (DHCP).
Red IP Trouble LED DS16 OFF (indicates no trouble present).
Yellow Operational LED D4 Blinks every 10 seconds (indicates normal operation).
Green RF Signal LED D3 Blinks at least 4 times (indicates minimally acceptable signal strength).
Red Trouble LED D5 OFF (indicates no trouble present).