Appendix B
Specifications
The following figures and tables provide specifications for each Unit of the C200HX/C200HG/C200HE. I/O Units
may take on one of two different shapes and are sometimes referred to as A-shape Units or B-shape Units.
Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape
Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of
these two shapes of I/O Unit.
General Specifications
Item Specifications
Power Supply
Unit
C200HW-PA204 C200HW-PA204S C200HW-PA204R C200H-PA209R C200HW-PD024
Supply voltage 100 to 120 VAC/200 to 240 VAC (50/60 Hz) 24 VDC
Operating voltage
range
85 to 132 VAC/170 to 264 VAC 19.2 to 28.8 VDC
Power
consumption
120 VA max. 180 VA max. 40 W max.
Inrush current 30 A max. 30 A max. at 100
to 120 VAC
40 A at 200 to
240 VAC
30 A max.
Output capacity
5 VDC, 4.6 A (including power supply to the CPU Unit) 5 VDC, 9 A
(including power
supply to the CPU
Unit)
5 VDC, 4.6 A
(including power
supply to the CPU
Unit)
26 VDC, 0.625 A
Total: 30 W
26 VDC, 0.625 A
24 VDC, 0.8 A
Total: 30 W
26 VDC, 0.625 A
Total: 30 W
26 VDC, 1.3 A
Total: 45 W
26 VDC, 0.625 A
Total: 30 W
Output terminals Without With
(see note 1)
Without Without
RUN output
(see note 5)
Without SPST-NO contact
Switching
capacity:
2 A at 250 VAC
(resistive load),
0.5 A at 250 VAC
(inductive load),
2 A at 24 VDC
SPST-NO contact
Switching
capacity:
2 A at 240 VAC
(resistive load),
0.5 A at 120 VAC
(inductive load),
2 A at 24 VDC
(resistive load), 2
A at 24 VDC
(inductive load)
Without
Insulation
resistance
AC: 20 M min. (at 500 VDC) between external terminals and GR terminal
(see note 2)
DC: 20 M min.
(at 500 VDC)
between external
terminals and GR
terminal (see note
2)
Dielectric strength
AC: 2,300 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
DC: 2,300 VAC,
50/60 Hz for 1
minute between
external terminals
DC: 1,000 VAC, 50/60 Hz for 1 minute between external terminals and GR
terminals with a leakage current of 10 mA max. (see note 2)
external
terminals
and GR terminals
with a leakage
current of 10 mA
max. (see note 2)

Table of Contents

Other manuals for Omron C200HG-CPU43

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron C200HG-CPU43 and is the answer not in the manual?

Omron C200HG-CPU43 Specifications

General IconGeneral
BrandOmron
ModelC200HG-CPU43
CategoryController
LanguageEnglish

Related product manuals