CSM_E5AN_E5EN_DS_E_4_6
1
Basic-type Digital Temperature Controller
E5AN/E5EN (96 x 96 mm and 48 x 96 mm)
New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with
Enhanced Functions and Performance.
Improved Indication Accuracy and
Preventive Maintenance Function.
Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
A PV/SV-status display function can be set to automatically
alternate between displaying the status of the Temperature
Controller (auto/manual, RUN/STOP, and alarms) and the
PV or SV.
Preventive maintenance for relays in the Temperature
Controller using a Control Output ON/OFF Counter.
Three-level display that simultaneously displays the PV, SV,
and MV.
One-touch operation with PF Key that can be assigned to
auto/manual, RUN/STOP, or other functions.
Main I/O Functions
96 × 96 mm
E5AN
48 × 96 mm
E5EN
Refer to Safety Precautions for E5
@
N/E5
@
N-H.
Refer to Operation for E5
@
N/E5
@
N-H for operating
procedures.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period
250 ms
PF Key
(Programmable function key)
Control Output 1
Relay output
Voltage output (for driving SSR)
Current output
Control Output 2
Voltage output
(for driving SSR)
Long-life relay
output (hybrid)
Auxiliary Outputs
Three
Auto/manual switching
Temperature Controller
status display
Simple program function
Control output ON/OFF
count alarm
PV change rate alarm
Models also available with
RS-485 or RS-232C
communications
E5AN E5EN
4-digit Display
3-level Display *
Simultaneously displays set items,
such as the PV, SV, and MV.
* A 2-level display when shipped from the factory. A
3-level display is activated if parameters are
initialized. For details on the third display level, refer
to the User’s Manual, Basic Type (Cat. No. H156).
Event Inputs
None
Two
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN/E5GN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals