Basic-type Digital Temperature Controller E5AN/E5EN 1
Basic-type Digital Temperature Controller
E5AN/E5EN (96 x 96 mm and 48 x 96 mm)
New 96 x 96-mm and 48 x 96-mm Basic Temperature Controllers with
Enhanced Functions and Performance.
Improved Indication Accuracy and
Preventive Maintenance Function.
Indication Accuracy
Thermocouple input: ±0.3% of PV (previous models: ±0.5%)
Pt input: ±0.2% of PV (previous models: ±0.5%)
Analog input: ±0.2% FS (previous models: ±0.5%)
A PV/SV-status display function can be set to alternate between
displaying the PV or SV and the status of the Temperature
Controller (auto/manual, RUN/STOP and alarms).
Preventive maintenance for relays using a Control Output
ON/OFF Counter.
Three-level display that simultaneously displays
the PV, SV, and MV.
One-touch operation with PF Key that can be assigned to
auto/manual, RUN/STOP, or other functions.
Main I/O Functions
96 × 96 mm
E5AN
48 × 96 mm
E5EN
Refer to Safety Precautions on page 18.
Sensor Inputs
• Universal thermocouple/Pt inputs
(Models with temperature inputs)
• Analog current/voltage inputs
(Models with analog inputs)
Indication Accuracy
• Thermocouple input: ±0.3% of PV
• Pt input: ±0.2% of PV
• Analog input: ±0.2% FS
Sampling Period and control update
250 ms
PF Key
(Programmab
le function key)
Control Output 1
Relay output
Voltage output (for driving SSR)
Current output
Control Output 2
Voltage output
(for driving SSR)
Long-life relay
output (hybrid)
3 auxiliary outputs
Auto/manual switching
Temperature Controller
status display
Simple program function
Control output ON/OFF
count alarm
PV change rate alarm
Models optional available
with RS-485 or RS-232C
communications
E
5
AN
E
5
EN
4 digit, 11 segments Display
3-line Display
Simultaneously displays set items,
such as the PV, SV, and MV.
A 2-line display when shipped from the factory. A
3-line display is activated if parameters are
initialized. For details on the third display level, refer
to the User’s Manual, Basic Type (Cat. No. H156).
Event Inputs
None
Two
This data sheet is provided as a guideline for selecting products. Be sure to refer to the following user manuals for application precautions
and other information required for operation before attempting to use the product.
E5CN/E5AN/E5EN Digital Temperature Controllers User's Manual Basic Type (Cat. No. H156)
E5CN/E5AN/E5EN Digital Temperature Controllers Communications Manual Basic Type (Cat. No. H158)

Other manuals for Omron E5AN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron E5AN and is the answer not in the manual?

Omron E5AN Specifications

General IconGeneral
BrandOmron
ModelE5AN
CategoryTemperature Controller
LanguageEnglish

Related product manuals