E5CSL/E5CWL
2
Ordering Information
Single Display
Dual Display
Accessories (Order Separately)
Terminal Cover
Front Panel
Note: 1. This Front Panel accessory is required to attach the Y92A-
48B or Y92A-48D.
2. This Front Panel accessory is only the frame.
It does not include the plastic cover.
Adapter
Note: 1. Use this Adapter when the Front Panel has already been
prepared for the E5B@.
2. Only black is available.
Specifications
Ratings
Size Power supply voltage Input type Alarm output Control output Model
1/16 DIN
48 × 48 × 60
(W × H × D)
100 to 240 VAC
Thermocouple
None
Relay output
E5CSL-RTC
Resistance thermometer E5CSL-RP
Thermocouple
Voltage output
(for driving SSR)
E5CSL-QTC
Resistance thermometer E5CSL-QP
Size Power supply voltage Input type Alarm output Control output New model
1/16 DIN
48 × 48 × 60
(W × H × D)
100 to 240 VAC
Thermocouple
1
Relay output
E5CWL-R1TC
Resistance thermometer E5CWL-R1P
Thermocouple
Voltage output
(for driving SSR)
E5CWL-Q1TC
Resistance thermometer E5CWL-Q1P
Model E53-COV19
Model E53-COV20
Model Y92F-45
Power supply voltage 100 to 240 VAC, 50/60 Hz
Operating voltage range 85% to 110% of rated supply voltage
Power con-
sumption
E5CSL 3.5 VA
E5CWL 3.5 VA
Sensor input
Models with thermocouple inputs
Thermocouple: K, J, T, R, or S
Models with platinum resistance thermometer inputs
Platinum resistance thermometer: Pt100
Control
output
Relay output SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
Voltage output
(for driving
SSR)
Output voltage: 12 VDC +25%/−15% (PNP), max. load current: 21 mA, with short-circuit protection circuit
Alarm output SPST-NO, 250 VAC, 1 A (resistive load), electrical life: 100,000 operations, minimum load: 5 V, 10 mA
Control method ON/OFF control or 2-PID control (with auto-tuning)
Setting method Digital setting using front panel keys
Indication method
7-segment digital display and individual indicators
Character height: E5CSL: 21.7 mm E5CWL: 16.2 mm (PV)
Other functions Temperature input shift, run/stop, protection functions, etc.
Ambient operating
temperature
−10 to 55°C (with no icing or condensation)
Ambient operating humidity 25% to 85%
Storage temperature −25 to 65°C (with no icing or condensation)