Description Model Specification
Output Unit E53-R Relay
E53-S SSR
E53-Q
Pulse (NPN) 12 VDC at 40 mA max.
E53-Q3
Pulse (NPN) 24 VDC at 20 mA max.
E53-Q4
Pulse (PNP) 24 VDC at 20 mA max.
E53-C3
Linear (4 to 20 mA) under a load of 600
Ω
max.
E53-C3D
Linear (0 to 20 mA) under a load of 600
Ω
max.
E53-V34
Linear (0 to 10 V) under a load of 1 k
Ω
min.
E53-V35
Linear (0 to 5 V) under a load of 1 k
Ω
min.
Note: The
Digital Controller uses a dedicated, high-resolution Output Unit. The E53-C Current Output Unit for the E5
j
X cannot be used with
the
Digital Controller
.
Description
Model Specification
Option Unit E53-AKB
Event input
E53-AK01
Communication (RS-232C)
E53-AK02
Communication (RS-422)
E53-AK03
Communication (RS-485)
E53-AKF T
ransfer output
Note: 1.
The Option Unit can be used either by the E5AK or E5EK.
2.
The E5AK allows a maximum of three Option Units to be mounted. Refer to page
13 for mounting combinations.
The E5EK allows only one Option Unit to be mounted.
Inspection Report
The Digital Controller can be provided together with an inspection report.
Refer to the following legend with the suf
fix “K” when ordering a model provided together with an inspection report.
E5jK-T
AA2-K, E5
jK-TPRR2-K
Accessories (Order Separately)
Name Model Hole
diameter
Current Transformer E54-CT1
5.8 dia.
E54-CT3
12.0 dia.
Note:
No CT is required unless the heater burnout alarm function is used.
Name Model
Connectable models
T
erminal Cover
E53-COV0809 E5AK
E53-COV08 E5EK
Unit Label
Model Y92S-L1
Ranges
Platinum Resistance Thermometer
Input
(switch selectable)
JPt100 Pt100
Range °C
–199.9 to 650.0 –199.9 to 650.0
°F
–199.9 to 999.9 –199.9 to 999.9
Setting 0 1
Thermocouple
Input (switch
selectable)
(see note)
K1 K2 J1 J2 T E L1 L2 U N R S B W PLII
Range °C
–200
to
1,300
0.0
to
500.0
–100
to
850
0.0 to
400.0
–199.9
to
400.0
0 to
600
–100
to
850
0.0 to
400.0
–199.9
to
400.0
–200
to
1,300
0 to
1,700
0 to
1,700
100
to
1,800
0 to
2,300
0 to
1,300
°F
–300
to
2,300
0.0 to
900.0
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
0 to
1,100
–100
to
1,500
0.0 to
750.0
–199.9
to
700.0
–300
to
2,300
0 to
3,000
0 to
3,000
300
to
3,200
0 to
4,100
0 to
2,300
Setting 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Note: Setting
number is factory-set to 2 (K1).