S8VS
Mode Change (S8VS-@@@24A@@/S8VS-@@@24B@@/S8VS-@@@24BE@ Only)
S8VS-@@@24A@@ models (with display monitor) can display the output voltage, output current, peak hold current, or maintenance forecast
monitor time. S8VS-@@@24B@@/S8VS-@@@24BE@ models (with display monitor) can display the output voltage, output current, peak hold
current, or total run time.
Power-ON
Model indication
Operation mode
Press and hold
Press Mode key and
Up key
U or Down Key D
hold for three seconds or more.
for three seconds or more.
Or no key operation for 30 seconds or more.
Setting mode
Note: No setting mode is provided for the S8VS-06024@.
Operation Mode
Various states of the Power Supply are indicated.
Models with Maintenance Forecast Monitor (S8VS-@@@24A@@)
Output voltage
(Voltage output by Power Supply is
monitored and displayed.)
Output current
(Current output by Power Supply is
monitored and displayed.)
Peak hold current (See note 1.)
(Maximum current output by Power Supply is
recorded and displayed.)
Maintenance forecast monitor
Models with Total Run Time Monitor (S8VS-@@@24B@@/
S8VS-@@@24BE@)
Output voltage
(Voltage output by Power Supply is
monitored and displayed.)
Output current
(Current output by Power Supply is
monitored and displayed.)
Peak hold current
(Maximum current output by Power Supply is
recorded and displayed.)
Total run time monitor
Note: 1. The peak hold current starts measuring the current 3 seconds after the Power Supply is started. Inrush current is thus not measured.
2. For the factory setting, the output voltage will be displayed when the power supply is first turned ON. Thereafter, the output voltage will
be indicated in the same display when shutting down.
Setting Mode (Except for S8VS-06024@)
Set various parameters of the Power Supply.
Models with Maintenance Forecast Monitor (S8VS-@@@24A@@) Models with Total Run Time Monitor (S8VS-@@@24B@@/S8VS-@@@24BE@)
Operation Mode
Operation Mode
Press 3 seconds or more or no key
pressed for 30 seconds or more.
or
Press 3 seconds
or more.
Press 3 seconds or more or no key
or
pressed for 30 seconds or more.
Press 3 seconds
or more.
*
*
/
/
Undervoltage
Undervoltage
18.5 to 20.0 to 27.5 (V) 18.5 to 20.0 to 27.5 (V)
detected
detected
0.1-V steps 0.1-V steps
*
*
/
/
Maintenance
Total run
0.0 to 0.5 to 5.0 (y)
1 to 50 to 150 ( ×
1000 h)
forecast
time
0.5-year steps
1,000-hour steps
* Factory settings are in reverse
* Factory settings are in
type.
reverse type.
Note: 1. Press and hold the (9) Up Key U or (10) Down Key D for two seconds or more to increase or decrease the value rapidly.
2. The S8VS-06024@ is not provided with the setting mode and its parameters are fixed at the shipment setting.
18