1. Vertical Airflow Direction
• The louver swings up and down as shown above.
• The louver does not swing when the Indoor Fan stops
during operation at the upper limit.
Heating Mode
• When the intake air temp. reaches 38°C, the louver is
changed from upper to lower limit. When the intake air
temp falls to 35°C, the louver is changed from lower to
upper limit.
2. Horizontal Airflow Direction
• The louver can be selected between 14° - 36° (as
shown above) when pressing Manual Airflow Direction
Selection Button.
• The louver can be selected between 0° - 61° (as shown
above) when pressing Manual Airflow Direction
Selection Button.
8.10. Airflow Direction Control
Cooling and Soft Dry Mode
• The left and right airflow direction louvers can be adjusted manually.
30