2.1.3. Indoor Fan Motor Operation (Page: 21)
Fan
Speed
No.
CS-E9BKP CS-E12BKP Remark
Voltage
(V)
Cooling Dry Heating Voltage
(v)
Cooling Dry Heating
5 3.15 3.23 - Auto operation mode judgment (H).
- ON timer preparation sampling (H).
- Sleep shift operation (H).
11 3.39 Me- 3.60 Me - Powerful Mode at Lo fan for E12BKP (C).
27 3.89 4.05 SHi
28 3.90 SHi 4.08
2.1.4. Heating Mode Indoor Fan Motor Operation (Anti Cold draft Control) (Page: 22 &
23)
Note:
1. UP:
•
If move from Lo or Lo-, the fan speed will be shifted to Maximum.
2.2. Protection Control Features
2.2.1. Indoor Power Relay Control (Page: 28)
However, during instantaneous power failure (< 0.5s), power relay will turn off. Then, it will turn on 3 minutes after power recover
and the unit will operate as previous operation condition.
2.2.2. Total Running Current Control (Page: 28)
1. When the total outdoor unit running current (AC) exceeds X value, the frequency instructed for compressor operation will be
decreased a step to smaller frequency number.
2. If the running current does not exceed X value for five seconds, the frequency instructed will be increased a step at one time
to bigger frequency number.
2.2.3. IPM (Power transistor) Prevention Control (Page: 29)
A. DC Peak Current Control
1. When electric current to IPM exceeds set value of 22.5 ± 3.5 A, the compressor will stop operate. Then, operation will restart
after three minutes.
2. If the set value is exceeded again within 30 seconds after the compressor starts, the operation will restart after one minute.
If this condition repeats continuously for seven times, all indoor and outdoor relays will be cut off.
4
CS-E9BKP CU-E9BKP5 / CS-E12BKP CU-E12BKP5