2
1-4. Connection Warnings
There is no standard backfeed protection inside of the UPS. However, there are relays on the Input to
cut off line voltage and while the neutral is still connect to UPS.
Main
Input
Input Rly
UPS
L1
L2
L3
N
Main
Input
Input Rly
UPS
L1
L2
L3
N
Bypass
Input
Input Rly
L1
L2
L3
N
Input relay diagram Input relay diagram for dual-input model
This UPS should be connected with TN grounding/earthing system.
The power input for this unit must be three-phase rated in accordance with the equipment nameplate. It
also must be suitably grounded.
Use of this equipment in medical instrument of any life-sustaining equipment where failure of this
equipment can reasonably be expected to cause the failure of the life-sustaining equipment or to
significantly affect its safety or effectiveness is not recommended. Do not use this equipment in the
presence of a flammable mixture with air, oxygen or nitrous oxide.
Connect grounding terminal of UPS to a grounding electrode conductor.
In accordance with safety standard EN-IEC 62040-1, installation has to be provided with aBackfeed
Protection system, as for example a contactor, which will prevent the appearance of voltage or
dangerous energy in the input mains during a mains fault (see figure 24 and respect the wiring diagram
of «Backfeed Protection» depending if the equipment is with signal or three phase input).
There can be no derivation in the line that goes from the «Backfeed Protection» to the UPS, as
the standard safety would be infringed.
Warning labels should be placed on all primary power switches installed in places away from the unit to
alert the electrical maintenance personnel of the presence of a UPS in the circuit. The label will bear the
following or an equivalent text:
Before working on this circuit
- Isolate Uninterruptible Power Supply (UPS)
- Then check for Hazardous Voltage between all terminals including the protected
earth
Risk of Voltage Backfeed
WARNING
HIGH LEAKAGE CURRENT
EARTH CONNECTION ESSENTIAL
BEFORE CONNECTING SUPPLY

Other manuals for PROLiNK MASTER II Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the PROLiNK MASTER II Series and is the answer not in the manual?

PROLiNK MASTER II Series Specifications

General IconGeneral
BrandPROLiNK
ModelMASTER II Series
CategoryUPS
LanguageEnglish

Related product manuals