13)
AC Input Voltage AC Eingangsspannung nom. AC 100-240V
15)
-15%/+10%
AC 200-240V
-15%/+10%
AC 100-240V
15)
-15%/+10%
AC 100-240V
15)
-15%/+10%
AC 200-240V
-15%/+10%
Input Frequency Eingangsfrequenz nom.
50-60Hz
±6%
50-60Hz
±6%
50-60Hz
±6%
50-60Hz
±6%
50-60Hz
±6%
AC Input Current
3)
AC Eingangsstrom
3)
typ. 8.6A / 4.5A - / 4.6A 8.6A / 4.5A 8.6A / 4.5A - / 4.6A
Power Factor
3)
Leistungsfaktor
3)
typ. 0.99 / 0.99 - / 0.96 0.99 / 0.99 0.99 / 0.99 - / 0.96
Allowed Voltage L or N to Earth Erlaubte Spannung L oder N zu Erde max. 300Vac 300Vac 300Vac 300Vac 300Vac
PFC Norm EN 61000-3-2 Class A PFC Norm EN 61000-3-2 Klasse A - Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
DC Input Voltage DC Eingangsspannung nom. - - - - -
Input Inrush Current
3) 4)
Einschaltspitzenstrom
3) 4)
typ. 17A / 11A peak - / 14A peak 17A / 11A peak 17A / 11A peak - / 14A peak
Hold-up Time
3)
Pufferzeit
3)
typ. 27ms / 27ms - / 30ms 27ms / 27ms 27ms / 27ms - / 30ms
Efficiency
3)
Wirkungsgrad
3)
typ. 93.6% / 94.6% - / 94.6% 93.5% / 94.6% 93.9% / 95.0% - / 95.0%
Power Losses
3)
Verlustleistung
3)
typ. 65.6W / 54.8W - / 54.8W 66.7W / 54.8W 62.4W / 50.5W - / 50.5W
Operational Temperature Range Betriebstemperaturbereich nom. -25°C - +70°C -25°C - +70°C -25°C - +70°C -25°C - +70°C -25°C - +70°C
Output Derating Leistungsrücknahme +60°C to +70°C 24W/°C 24W/°C 24W/°C 24W/°C 24W/°C
Storage Temperature Range Lagertemperaturbereich nom. -40°C - +85°C -40°C - +85°C -40°C - +85°C -40°C - +85°C -40°C - +85°C
Humidity
5)
Feuchte
5)
IEC 60068-2-30 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H. 5 - 95% r.H.
Vibration Schwingen IEC 60068-2-6 1g
10)
1g
10)
1g
10)
1g
10)
1g
10)
Shock Schocken IEC 60068-2-27 15g 6ms,
10)
10g 11ms
10)
15g 6ms,
10)
10g 11ms
10)
15g 6ms,
10)
10g 11ms
10)
15g 6ms,
10)
10g 11ms
10)
15g 6ms,
10)
10g 11ms
10)
Degree of Pollution Verschmutzungsgrad IEC 62103 2
5)
2
5)
2
5)
2
5)
2
5)
Degree of Protection Schutzart EN 60529 IP20 IP20 IP20 IP20 IP20
Class of Protection Schutzklasse IEC 61140 I
6)
I
6)
I
6)
I
6)
I
6)
Over-temperature Protection Übertemperaturschutz OTP Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
Output Over-voltage Protection Überspannungsschutz am Ausgang OVP, max. 32Vdc 32Vdc 48Vdc 60Vdc 60Vdc
Return Voltage Resistance
8)
Rückspeisefestigkeit
8)
max. 35Vdc 35Vdc 50Vdc 63Vdc 63Vdc
Leakage Current
7)
TN, TT-mains
IT-mains
PE- Ableitstrom
7)
TN, TT-Netze
IT-Netze
max.
max.
0.71mA / 1.18mA
1.73mA / 2.82mA
- / 0.75mA
- / 1.74mA
0.71mA / 1.18mA
1.73mA / 2.82mA
0.71mA / 1.18mA
1.73mA / 2.82mA
- / 0.75mA
- / 1.74mA
Parallel Use
11)
Parallelschaltbar
11)
- Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
Serial Use
12)
Serienschaltbar
12)
- Yes / Ja Yes / Ja Yes / Ja Yes / Ja Yes / Ja
Dimensions
9)
(WxHxD) Abmessungen
9)
(BxHxT) nom. 125x124x127mm 125x124x127mm 125x124x127mm 125x124x127mm 125x124x127mm
Weight Gewicht max. 1900g, 4.2lb 1800g, 4lb 1900g, 4.2lb 1900g, 4.2lb 1800g, 4lb
1) All parameters are specified at 230Vac input voltage, nominal output current, “Single Use”
setting, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
2) 50-Ohm measurement, bandwidth 20MHz
3) at 120Vac / 230Vac
4) Input inrush current is electronically limited, temperature independent and is valid for mains
interruptions > 1s
5) Do not energize while condensation is present.
6) PE connection required (Ground).
7) Leakage current at 132Vac, 60Hz / 264Vac, 50Hz
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the
power supply. The figure represents the maximum allowed feed back voltage
9) Depth without DIN-rail.
10) Higher levels possible when utilizing the wall mounting bracket ZM2.WALL
11) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more
than three units are paralleled.
12) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
13) Hiccup
PLUS
is an overload behavior with a balanced power management. In normal mode it
provides generous power reserves but effectively protects connected equipment and cables
against damage in the event of failure. More details on the next pages.
14) BonusPower
®
: The short-term power is available for 4s. After this, the output power will be
automatically reduced to the continuous output power level
15) An output current derating might be necessary at input voltages below 90Vac, see figure 5
1) Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, „Single-Use“ Modus,
25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, falls nichts anderes angegeben.
2) 50-Ohm Messung, Bandbreite 20MHz
3) bei 120Vac / 230Vac
4) Der Einschaltstromstoß ist elektronisch begrenzt, temperaturunabhängig und gilt für
Netzunterbrechungen > 1s
5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils
rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.
9) Tiefe ohne DIN-Schiene
10) Höhere Werte sind bei Verwendung des Wandmontageadapters ZM2.WALL möglich
11) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten
wird eine Sicherung oder eine Diode zur Entkopplung benötigt.
12) Nur für gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) Hiccup
PLUS
ist ein Überlastverhalten mit einem ausgewogenem Leistungsmanagement,
welches im Normalbetrieb kurzzeitig großzügige Leistungsreserven zur Verfügung stellt, aber
im Fehlerfall angeschlossene Verbraucher und Kabel effektiv vor Schäden schützt. Mehr
Informationen auf den nächsten Seiten.
14) BonusPower
®
: Wird dir Kurzzeitleistung für länger als 4s entnommen, reduziert sich die
maximal entnehmbare Ausgangsleistung auf die Dauerleistung
15) Unterhalb 90Vac kann eine Leistungsrücknahme erforderlich sein. Siehe Bild 5
Terminals and Wiring
Use appropriate copper cables that are designed for a minimum operating temperature of:
60°C for ambient temperatures up to 45°C,
75°C for ambient temperatures up to 60°C and
90°C for ambient temperatures up to 70°C.
Follow national installation codes and regulations! Ensure that all strands of a stranded wire enter
the terminal connection! Ferrules are allowed.
Input Output Signals
Solid wire 0.5-6mm
2
0.5-16mm
2
0.15-1.5mm
2
Stranded wire 0.5-4mm
2
0.5-10mm
2
0.15-1.5mm
2n
American wire gauge AWG 20-10 AWG 22-8 AWG 26-14
Max. wire diameter 2.8mm 5.2mm 1.5mm
(including ferrules)
Wire stripping length 7mm / 0.28inch 12mm / 0.5inch 7mm / 0.28inch
Tightening torque 1Nm / 9lb.inch 2.3Nm / 20.5lb.inch Spring-clamp terminal
Anschlussklemmen und Verdrahtung
Verwenden Sie geeignete Kupferkabel, die mindestens für:
60°C bei einer Umgebungstemperatur bis zu 45°C,
75°C bei einer Umgebungstemperatur bis zu 60°C und
90°C bei einer Umgebungstemperatur bis zu 70°C zugelassen sind.
Beachten Sie nationale Bestimmungen und Installationsvorschriften! Stellen Sie sicher, dass
keine einzelnen Drähte von Litzen abstehen. Aderendhülsen sind erlaubt.
Eingang Ausgang Signale
Starrdraht 0,5-6mm
2
0,5-16mm
2
0,15-1,5mm
2
Litze 0,5-4mm
2
0,5-10mm
2
0,15-1,5mm
2
AWG AWG 20-10 AWG 22-8 AWG 26-14
Max. Drahtdurchmesser 2,8mm 5,2mm 1,5mm
(inklusive Aderendhülsen)
Abisolierlänge 7mm / 0,28inch 12mm / 0,5inch 7mm / 0,28inch
Anzugsdrehmoment 1Nm / 9lb.inch 2.3Nm / 20,5lb.inch Federkraftklemme