EasyManuals Logo
Home>Pylontech>Storage>Force-H1-V2

Pylontech Force-H1-V2 User Manual

Pylontech Force-H1-V2
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #37 background imageLoading...
Page #37 background image
33
*It`s suggested to use P-Combiner-HV-6 for upto 6 strings, max. 100Amps synchronized
continuous operation.
*It`s not allowed to use the P-Combiner-HV-6 or similar concept of multi-groups connection
method in case the multiple groups` of battery are operation independently.
Make sure to have the D+ & D- plug into the combiner box properly.
Wiring diagram of master/slave communication cable
The communication for master/slave string connection shall use a 8pin pin-pin RJ45 cable,
connecting from first BMS Link 1 to second BMS Link 0, then from second BMS Link 1 to third BMS
link 0 (if has), all the way to the last BMS Link 0. The BMS with Link Port 0 EMPTY is defined as the
Master string, which further communication with the inverter or upper controller.
The slave strings` CAN/RS485 Port is ineffective in this case.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pylontech Force-H1-V2 and is the answer not in the manual?

Pylontech Force-H1-V2 Specifications

General IconGeneral
BrandPylontech
ModelForce-H1-V2
CategoryStorage
LanguageEnglish

Related product manuals