Trouble shooting
Communication related problems:
1
)Baud rate selection
Solution: Check the dip switch 1 on the battery. If
the baud rate of the communication is 9600, the dip
switch 1 should be 1,If the baud rate is 115200, the
dip switch 1 should be 0.
2) Cable connections
Solution: Check the cable connections, including
communication methods, link ports.
3) Pin definitions of communication cables
Solution: Please refer to pin definition diagrams.
Functional related problems:
1) Battery over discharged
Solution: Please use a DC charger
to charge the battery.
2) Cell voltages imbalance
Solution: Please use a DC charger
(around 1 – 2 Amps) to balance the
battery cell voltages.
3) BMS error
Solution: Please swap the BMS or
use BatteryView to clear the BMS
error.