Quest 105/155/205/ 225 Dual Installation, Operation and Maintenance Instructions
10
www.QuestHydro.com
info@QuestHydro.com
7.2 Technical Description
The Quest Dual Dehumidifier uses a refrigeration system similar to an air conditioner's to remove heat and moisture from
incoming air, and add heat to the air that is discharged.
Hot, high-pressure refrigerant gas is routed from the compressor to the condenser coil. The refrigerant is cooled and condensed
by giving up its heat to the air that is about to be discharged from the unit. The refrigerant liquid then passes through a filter/
drier and capillary tubing which causes the refrigerant pressure and temperature to drop. It next enters the evaporator coil
where it absorbs heat from the incoming air and evaporates. The evaporator operates in a flooded condition, which means that all
the evaporator tubes contain liquid refrigerant during normal operation. A flooded evaporator should maintain nearly constant
pressure and temperature across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the accumulator after leaving the evaporator coil. The accumulator prevents any
liquid refrigerant from reaching the compressor. The compressor evacuates the cool refrigerant gas from the accumulator and
compresses it to a high pressure and temperature to repeat the process.
7.3 Troubleshooting
Neither fan nor compressor running. Dehumidification is being called for. No fan call.
1. Unit unplugged or no power to outlet.
2. Humidity control set too high.
3. Loose connection in internal or control wiring.
4. Defective Compressor relay.
5. Defective control transformer.
Compressor is not running. Dehumidification is being called for. No fan call.
1. Defective compressor run capacitor.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor.
5. Defrost thermostat open.
Compressor cycles on and o. Dehumidification is being called for. No fan call.
1. Low ambient temperature and/or humidity causing unit to cycle through defrost mode.
2. Defective compressor overload.
3. Defective compressor.
4. Defrost thermostat defective.
5. Dirty air filter(s) or air flow restricted.
Fan is not running. Dehumidification or fan is being called for.
1. Loose connection in fan circuit.
2. Obstruction prevents fan impeller rotation.
3. Defective fan.
4. Defective fan relay.