Warning
Please Note
The specifications of the product detailed on this
Set-Up Guide may change without notice. RDM
Ltd. shall not be liable for errors or for incidental
or consequential damages, directly and indirectly,
in connection with the furnishing, performance or
misuse of this product or document.
Inputs and outputs
Selecting this menu option allows the user to view the inputs and outputs. Use the up/down button to select the desired input or output
and then press “Enter”. The value will be shown on the display. See View IO
Units
Use this to select the temperature probe type.
0 = PT1000 (Deg C)
1 = PT1000 (Deg F)
2 = NTC2K (Deg C)
(Default)
3 = NTC2K (Deg F)
4 = NTC2K25 (Deg C)
5 = NTC2K25 (Deg F)
6 = NTC10K (Deg C)
7 = NTC10K (Deg F)
Disp
Display setting: -
0 = Decimal display (1 place)
1 = Integer Display
Type
The controller has only one type so cannot be changed.
Relay Assignment
Relay 1 Fans Use N/O contact
Relay 2 Thermostat Stage 1 Use N/O contact
Relay 3 Thermostat Stage 2 Use N/O contact
Relay 4 Thermostat Stage 3 Use N/O contact
Relay 5 Thermostat Stage 4 Use N/O contact
ID
Sets the controller ID, (normally used in conjunction with the IP-L network mode). Set a number in the range of 1 – 999
RTC
Real time clock (This will automatically synchronise on network systems)
a. Use the up or down buttons to scroll through the display until the display reads “rtc”
b. Press enter. The display will show “t-1”. press enter again
c. Scroll hours up or down (0 – 23) press enter
d. Use up button to select “t-2”, press enter
e. Scroll minutes up or down (0 – 59) press enter
f. Repeat for t-3 (seconds 0 – 59)
g. Repeat for t -4 (Days up to 31)
h. Repeat for t -5 (months up to 12)
i. Repeat for t -6 (Year up to 99)
j. Use up button to display “ESC”, press enter to display “rtc”.
Hub/Switch Type
Select the desired value for the type of communication module in use.
0 = Mercury Hub/Switch
1 = ML Hub/Switch