EasyManuals Logo
Home>Rheem>Swimming Pool Heater>P-M407

Rheem P-M407 User Manual

Rheem P-M407
56 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
46
Power On
Is the water
t
emperature displayed?
NO
YES
Push MODE
switch to select
"
Pool" or "Spa"
Push Temp
arrow to scroll to
desired temperature
NO
Water temperature
and set
temperature
displayed?
YES
Heating” will
display briefly
NO
NO
YES
YES
Flame icon displayed
and flashing?
OR
Water temp displayed?
(pilot lit and rectified)
Heater Fired?
END
• Check On/Off switch (under lid on control panel)
Check for 120/240 volts to the transformer
(time clock, circuit breaker, wire connections)
• Check for 24 volts to Circuit Board (P6 connector)
Remote” and Water Temperature displayed
(a remote control is controlling the heater)
N
ote: Disconnect the remote by turning the
remote function off. See page 36 for instructions.
NO
YES
Is a fault code displayed and flashing?
Diagnostic Readouts
Sensor Failure,” “Sensor Open” or “Sensor Short” -
Temperature sensor out of range (replace sensor)
Verify power at MV on P-4 Terminal on digital circuit board.
Verify power to valve MV voltage. (Replace valve.)
Spark
Sensor Failure
Inspect thermister, wires, and connector at Terminal P1
Check resistance value of the thermister. Reference to chart below.
Replace thermister if not within 10% of values shown below.
If okay, replace Circuit Board.
Temp Degrees F 40 50 60 70 80 90 100 106
Resistance (k)
261.1 199.0 153.1 118.8 93.0 73.3 58.3 51.0
If okay, replace Circuit Board
Sensor resistance at various temperatures
Water Sw Open Pressure switch. Verify water flow and pressure
CLEAN FILTER / STRAINER - backwash if neccessary.
Hi Limit 1 Fault High limit switch. Verify water flow. Inspect internal
Hi Limit 2 Fault Thermostat (Unitherm Governor) and bypass valve.
Rollout Sw Open Rollout Sensor - Check for blocked heat exchanger and soot.
Atmospheric Units - Replace fusible link.
Lo NOx Units - Press manual reset button.
Clock/Fireman Sw Fireman or Remote switch connected to safety loop is in the
OFF mode.
Vent/Field Sw #1 Vent switch open. Check connections to the board.
If extractor installed, troubleshoot extractor.
Ignition Lockout Ignition lockout. Check power at pilot valve. Check spark (bad
ignition circuit or hi-tension wire). Verify clean pilot orifice and
clearance from igniter to ground hood.
Ignition Failure Ignition failure. Verify gas to the heater. Verify valve operation
(gas present at tube fitting).
C
ONTROL LOGIC - FLOW CHART

Table of Contents

Other manuals for Rheem P-M407

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rheem P-M407 and is the answer not in the manual?

Rheem P-M407 Specifications

General IconGeneral
BrandRheem
ModelP-M407
CategorySwimming Pool Heater
LanguageEnglish

Related product manuals