12
INSTALLATION
Interconnecting Tubing (cont�)
Interconnecting Tubing and
Fitting Losses
Refrigerant tubing is measured in terms of actual
length and equivalent length� Actual length is used
for refrigerant charge applications� Equivalent
length takes into account pressure losses from
tubing length, ttings, vertical separation, acces-
sories, and lter dryers. The table below references
dierent commonly used equivalent lengths.
Equivalent Length for Fings ()
Line Size
(in)
90° Short
Radius
Elbow
90° Long
Radius
Elbow
45°
Elbow
Solenoid
Valve
Check
Valve
Site
Glass
Filter
Dryer
3/8 1.3 0.8 0.3 6 4 0.4 6
1/2 1.4 0.9 0.4 9 5 0.6 6
5/8 1.5 1 0.5 12 6 0.8 6
3/4 1.9 1.3 0.6 14 7 0.9 6
7/8 2.3 1.5 0.7 15 8 1 6
1-1/8 2.7 1.8 0.9 22 12 1.5 6
Liquid Line Selection
The purpose of the liquid line is to transport warm
sub-cooled liquid refrigerant from the outdoor unit
to the indoor unit� It is important not to allow the
refrigerant to ash any superheated vapor prior
to the expansion device of the indoor coil� The
ashing of refrigerant can occur for the following
reasons:
Low refrigerant charge
Improperly selected liquid line size
Absorption of heat prior to expansion device
Excessive vertical rise between the condenser
and evaporator
Table 2 lists the equivalent length per 25’ of liquid
line at various diameters up to 300’� The total pres-
sure drop allowed for the liquid line is 50 PSI� The
procedure for selecting the proper liquid line is as
follows:
Measure the total amount of vertical rise
Measure the total amount of liquid line needed
Add all of the equivalent lengths associated with
any ttings or accessories using the table above.
Add the total length and tting pressure drop.
This will equal your total equivalent length�
Round-down the total equivalent length to the
closest value in Table 2�
Reference Table 2 to verify the round-down val-
ue of the calculated equivalent length is compat-
ible with the required vertical rise and diameter
of liquid line�
Table 1
Note: Elevaon is defined as the
highest point of the line set to the
lowest
Figure 1
Tubing