13
USER’S INFORMATION MANUAL
COMBI BOILERS 99
-
125
-
160
-
199
MAINTENANCE
General Care
Keep combustible materials and ammable liquids and vapors away from the unit.
Keep vent terminals clear of obstructions (snow, dirt, etc.).
Regular Maintenance
Check the domestic hot water temperature at the faucet to ensure the
temperature is not too hot. If the temperature is too hot, you can adjust the
water temperature with the unit’s controller. If these adjustments are not
correcting the issue, call your qualied service technician for service.
Check the pressure relief valves and discharge piping for signs of leakage
or moisture. If water or moisture is found, contact your qualied service
technician as soon as possible for service.
Examine the condensate trap every two months to see if cleaning is
necessary. Ensure that the trap has been re-lled completely before ring
the unit. The outlet hose may be connected to a condensate neutralizer, if so,
check the pH of the water coming out of the neutralizer is above 6.0pH. If the
pH is below 6.0 then the neutralizer will need to be re-charged or replaced.
Contact your qualied service technician for service.
Annual Maintenance
The unit must be inspected by your qualied service technician for the following:
Inspect the ue gas exhaust and air intake connections. All connections
should be tight and leak free.
Inspect ue gas exhaust piping, combustion air piping and terminations.
Inspect the unit’s interior and vacuum if required.
Check for water, gas and condensate leaks in the unit and around the unit.
Check the condensate trap and clean if required. Re-ll the trap and re-install.
Check the water pressure.
Check water chemistry including water treatment level and/or propylene glycol
level if used.
Check the electrical connections.
Check the ignition electrode and remove oxidation from the electrode.
Replace if necessary.
Check the gas valve and ignition cable.
Check the controller settings.
Check the burners ame. Should be a quick and quiet ignition across the full
burner.
If required, clean the heat exchanger and the burner.
WARNING
Annual Maintenance must
only be done by a qualied
service technician.