56
008082013GW
See additional
definitions below
PARA 36 E Combi. setting definitions
00 = activation by temperature drop for DHW (no plate warming)
10 = activation by temperature drop for DHW (plus plate warming)
20 = flow switch activation only DHW. (No plate warming/ no temp actuation)
In either setting above - 00 or 10 the Flow switch is still in the circuit and if it sticks "closed" it can keep the boiler locked
in DHW and code 6 with appear on the screen. Unplug flow switch as it is not needed. (Do not waste time taking switch
out and cleaning it, just unplug it electrically)
PARA 36 Q combi
01 = factory setting-load sharing "on"
00 = Alternate setting - Load sharing "off" (MCBA thinks a "grey" non-modulating valve is being used in place of the
"Black" modulating valve) All other combinations are NOT to be used on Q
-
combi boilers)