Rockwell Automation Publication 22HIM-QR001G-EN-P - August 2021 5
PowerFlex 4-Class HIM (DSI) Quick Reference
14 [Ref Dec Position]
Sets the number of digits to be displayed to the right of the decimal point for the Reference.
Default: 1
Minimum: 0
Maximum: 3
Type: Read/Write
15
16
17
18
19
20
21
22
[Ref Units Char 1]
[Ref Units Char 2]
[Ref Units Char 3]
[Ref Units Char 4]
[Ref Units Char 5]
[Ref Units Char 6]
[Ref Units Char 7]
[Ref Units Char 8]
Selects up to 8 characters (from the ISO 8859-1 character set) to use for the Reference units on the Process Display.
Parameters 15…22 can also be configured using the ‘Edit Ref Text’ selection in the HIM Setup tab.
Default: 72(‘H’)
Default: 122(‘z’)
Default: 32(blank - no character)
Default: 32(blank - no character)
Default: 32(blank - no character)
Default: 32(blank - no character)
Default: 32(blank - no character)
Default: 32(blank - no character)
Minimum: 32
Maximum: 255
Type: Read/Write
23 [AUTO MAN Switch]
Switch the display of AUTO and MAN.
Default: 0 = Switch
Values: 0 = Switch
1 = Not Switch
Type: Read/Write
New settings to HIM parameters are implemented immediately. Resetting the HIM is not required for new values to take effect.