MODELF67Q/F71Q/F68Q/F69Q/F116Q/F117Q
6
process can be adjusted.
1.3. Service Conditions
Runxin Valve should be used under the below conditions:
Items Requirement
Working
Conditions
Water pressure 0.15MPa0.6MPa
Water temperature 5℃~50
Working
Environment
Environment
temperature
5℃~50
Relative humidity ≤95%(25)
Electrical facility AC100240V/5060Hz
Inlet Water
Quality
Water turbidity
Filter20FTU
Down-flow regeneration5FTU
Water hardness
+
Second Grade Na
+
10mmol/L
Free chlorine 0.1mg/L
Iron
2+
0.3mg/L
CODMn 2mg/L(O
2
)
In the above table, First Grade Na
+
represents First Grade Na
+
Exchanger. Second Grade Na
+
represents Second Grade Na
+
Exchanger.
When the water turbidity exceeds the conditions, a filter should be
installed on the inlet of control valve.
When the water hardness is exceeds the conditions, the outlet water
hardness will hardly reach the requirement of boiler feed water
(0.03mmol/L). It is suggested to adopt second grade softener.