PDS33 Series
Incorrect settings of motor
parameters
Set motor parameters
according to motor plate
Parameters writing
& reading failure
Change another board or
look for technical support
Ask for technical support
Water shortage of water source
Stop the controller Repair
broken wiring or replace
water level switch
Verify if the setting of FD.12
"Water shortage detection
current ratio" is too high, while
FD.10 "Water shortage detection
time" is non-zero and the current
sensing is enabled.
Reduce setting value of
FD.12
Accumulated running time
reached set value
Accumulated powering time
reached set value
PID feedback loss
when running
Abnormal PID feedback signal
PID feedback signal is below
detect value
Adjust PID feedback detect
value and detect time
Overtime fault of
fast-current limit
Load too heavy or motor stuck
Reduce load,or check the
motor
Rate of controller too small
Change upper rate controller
Poor contact between keyboard
and control board