EasyManuals Logo
Home>Sanyo>Air Conditioner>CH3642

Sanyo CH3642 User Manual

Sanyo CH3642
202 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #130 background imageLoading...
Page #130 background image
II - 10
SM830082
1
2
3
4
Section
5
2. Processes and functions
2-8 Discharge Temperature Control (Cooling and Heating)
This function prevents the compressor motor from burnout by overheating.
OUTDOOR
FAN SPEED
DISCHARGE GAS
TEMP. (°F)
239
(24, 36 Type)
221
203
200
194
185
275
(42 Type)
257
239
235
230
221
COMPRESSOR
ELECTRONIC REF.
CONTROL VALVE
(DISCHARGE TEMP.)
TRIP IS OPERATED.
H OR M
L
1928_THS_I
OPENOPEN
H OR M
ON
Fig. 11
Chart Summary and Explanations
Discharge temperature is sensed by TH8 (discharge gas sensor).
When the temperature rises above 203°F (24, 36 Type) the electronic refrigerant control
valve opens at 50 steps/30 seconds until the temperature falls below 200°F (24, 36 Type) .
During HEATING operation, when the temperature rises above 221°F (24, 36 Type), the
control circuit stops the outdoor fan motor until the temperature falls below 194°F (24, 36
Type). Please note that this control does not function during COOLING operation.
For both COOLING and HEATING modes, if the temperature reaches 239°F (24, 36 Type)
the operation shuts down and alarm P3 appears on the remote controller.
The outdoor fan speed is controlled on discharge temp. at heating mode.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Sanyo CH3642 and is the answer not in the manual?

Sanyo CH3642 Specifications

General IconGeneral
BrandSanyo
ModelCH3642
CategoryAir Conditioner
LanguageEnglish

Related product manuals