Configuration
4.5 Configuration with device connectors
SIRIUS 3RM1 motor starter
Manual, 11/2013, A5E0345285095020A/RS-AB/002
67
4.5
Configuration with device connectors
4.5.1
Configuration with device connectors
The device connector may be used only with the 24 V DC version of the motor starter. There
must be no mixing of the Standard and Failsafe variants of the 3RM1 motor starter via the
device connector. If both variants are used, these must be fitted on separate device
connector systems. This has no influence on the infeed system for the 3RM19 main circuit,
which can still be used without restriction for a combination of the variants.
For additional information on using device connectors, refer to "FAQs on the 3RM1 motor
starter (http://support.automation.siemens.com/WW/view/de/81525494)".
4.6
Examples/applications
4.6.1
Operation with the EMERGENCY-STOP function
The 3RM11 Failsafe and 3RM13 Failsafe safety-related motor starters can be used with any
safety relays and safety-related controllers in safety-related applications up to SILCL 3 in
accordance with IEC 62061, PL e/Cat. 4 in accordance with EN ISO 13849-1.