&RPPLVVLRQLQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
9-32 A5E00105492-03
 'LUHFW'DWD([FKDQJH
5HTXLUHPHQW
In 67(3 V 5.x or later, you can configure "Direct data exchange" for PROFIBUS
nodes. CPUs 31x-2 DP/31xC-2 DP can participate in direct data exchange both as
a sending or receiving station.
'HILQLWLRQ
"Direct data exchange" is a special communication relationship between
PROFIBUS-DP nodes.
Characteristic of direct data exchange is that PROFIBUS DP nodes "listen" on the
bus for data a DP slave returns to its DP master. This mechanism allows "Listening
stations" (receivers) direct access to modified input data of remote DP slaves.
$GGUHVVDUHDV
In your 67(3 configuration of the relevant peripheral input addresses, specify
which address area of the receiving station is to receive data requested from the
sending station.
A CPU 31x-2 DP/31xC-2 DP can operate as a:
DP slave sending station
receiving station, as DP slave or DP master, or as CPU not integrated in a
master system.

Table of Contents

Other manuals for Siemens CPU 314

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens CPU 314 and is the answer not in the manual?

Siemens CPU 314 Specifications

General IconGeneral
BrandSiemens
ModelCPU 314
CategoryController
LanguageEnglish

Related product manuals