Commissioning notes
When commissioning the plant, when carrying out maintenance work, or after longer off
periods, make the following safety checks:
Safety check to be carried out
Anticipated response
a)
Burner startup with flame detector
Lockout at the end of «TSA»
darkened
b)
Burner startup with flame detector
Lockout after approx. 40 seconds
exposed to extraneous light
c) Simulation of flame failure during
operation. For that purpose, darken the
flame detector during operation and
maintain this state
Repetition followed by lockout at
the end of «TSA»
Standards and certificates
Applied directives:
Low-voltage directive 2006/95/EC
Electromagnetic compatibility EMC 2004/108/EC
(immunity) *)
*) The compliance with EMC emission requirements must be checked after the burner control
is installed in equipment
Compliance with the regulations of the applied directives is verified by the
adherence to the following standards / regulations:
Household and similar electrical appliances - Safety
Electrical equipment of non-electric heated cooking and heating
appliances
The relevant valid edition of the standards can be found in the declaration
of conformity!
Note on DIN EN 60335-2-102
Household and similar electrical appliances - Safety - Part 2-102:
Particular requirements for gas, oil and solid-fuel burning appliances having electrical
connections. The electrical connections of the LOA and the AGK11 comply with the
requirements of EN 60335-2-102.
EAC Conformity mark (Eurasian Conformity mark)
ISO 9001:2008
ISO 14001:2004
OHSAS 18001:2007
China RoHS
Hazardous substances table:
http://www.siemens.com/download?A6V10883536
Service notes
The service adapters can only be used for a short time. They may only be used in
supervised operation by qualified staff.
4/16
Building Technologies Division CC1N7118en
19.05.2016
VDE 0700
VDE 0722

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens LOA26.171B27 and is the answer not in the manual?

Siemens LOA26.171B27 Specifications

General IconGeneral
BrandSiemens
ModelLOA26.171B27
CategoryController
LanguageEnglish

Related product manuals