2 / 14
Siemens RDF301. / RDF301.50 / RDF600KN CE1N3171en
Building Technologies Semi flush-mount room thermostats with KNX communications 2012.10-04
Additional RDF301.50 features:
Four buttons to control KNX actuators via KNX S-mode
(functions: switching, dimming, blinds control, 8-bit scene)
Type of mounting / suitable conduit boxes
RDF600KN for round box, with min 60 mm diameter, min 40 mm depth
RDF301... for recessed rectangular box with 60.3 mm fixing centers
Use
Room temperature control (heating or cooling) in individual rooms and zones by
means of:
2-pipe fan coil units
2-pipe fan coil units with electrical heater
4-pipe fan coil units
Compressors in DX-type equipment
Compressors in DX-type equipment with electrical heater
The RDF301... / RDF600KN controls:
One single or 3-speed fan
One or two on/off valve actuators
One on/off valve actuator and one 1-stage electrical heater
One 3-position valve actuator
One 1-stage compressor in DX-type equipment, or one 1-stage compressor with
electrical heater
Used in systems with:
Heating or cooling mode
Automatic heating/cooling changeover
Manual heating/cooling changeover
Heating and cooling mode (e.g. 4-pipe system)
The room thermostats are delivered with a fixed set of applications.
The relevant application is selected and activated during commissioning using one
of the following tools:
Synco ACS
ETS
Local DIP switch and HMI
Functions
Maintain room temperature via built-in temperature sensor or external room
temperature / return air temperature sensor
Changeover between heating and cooling mode (automatic via local sensor or
bus, or manual)
Select application via DIP switches or commissioning tool (ACS, ETS)
Select operating mode via operating mode button on the thermostat
Temporary Comfort mode extension
Single speed or 3-speed fan control (automatic or manual)
Display current room temperature or setpoint in °C and/or °F
Minimum and maximum limitation of room temperature setpoint
Button lock (automatic and manual)