Chapter 5
Technical Specifications
RUGGEDCOM RSG909R
Installation Guide
30 Failsafe Alarm Relay Specifications
Non Hazardous Environments
Input Voltage
Power
Supply Type
Minimum Maximum Nominal
Internal
Fuse Rating
Isolation
Maximum Power
Consumption
b
LO 10 VDC 60 VDC
12 VDC, 24
VDC, 48 VDC
5 A 1.5 kVDC 13.4 W
88 VDC 300 VDC
125 VDC,
250 VDC
3.15 A 5 kVDC 15.3 W
HI
85 VAC 264 VAC
110 VAC,
220 VAC
3.15 A 5 kVDC 15.5 W
b
Current consumption may vary based on configuration.
Section5.2
Failsafe Alarm Relay Specifications
Hazardous Environments
Maximum Switching Voltage
Rated Switching
Current
Isolation
30 VDC 2 A 5.0 kVAC
c
between coil and contacts
1.0 kVAC
c
between contacts
250 VAC 2 A 5.0 kVAC
c
between coil and contacts
1.0 kVAC
c
between contacts
c
50 to 60 Hz for 1 minute
Non Hazardous Environments
Maximum Switching Voltage
Rated Switching
Current
Isolation
300 VDC 2 A 5.0 kVAC
d
between coil and contacts
1.0 kVAC
c
between contacts
264 VAC 2 A 5.0 kVAC
c
between coil and contacts
1.0 kVAC
c
between contacts
d
50 to 60 Hz for 1 minute
Section5.3
Supported Networking Standards
Standard 10 Mbps Ports 100 Mbps Ports 1000 Mbps Ports Description
IEEE 802.3u
ü
IEEE 802.3x
ü ü ü
Flow Control