Certification
6.2EMC and Environmental Type Tests
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Require-
ments
6.2 EMC and Environmental Type Tests
The RUGGEDCOM RX1501 has passed the following Electromagnetic Compatibility
(EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test Description Test Levels Severity
Levels
Enclosure Contact ± 8 kVIEC 61000-4-2 ESD
Enclosure Air ± 15 kV
4
IEC 61000-4-3 Radiated RFI Enclosure Ports 20 V/m
Signal ports ± 4 kV @ 2.5 kHz
Note
a
DC Power Ports
AC Power Ports
IEC 61000-4-4 Burst (Fast Transient)
Earth ground ports
± 4 kV 4
Signal ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
DC Power Ports ± 2 kV Line-to-Ground
± 1 kV Line-to-Line
3
IEC 61000-4-5 Surge
AC Power Ports ± 4 kV Line-to-Ground
± 2 kV Line-to-Line
4
Signal ports
DC Power Ports
AC Power Ports
IEC 61000-4-6 Induced (Con-
ducted) RFI
Earth ground ports
10 V 3
100 A/m, continuous
1000 A/m for 1 s
Note
a
IEC 61000-4-8 Magnetic Field Enclosure Ports
1000 A/m for 1 s 5
IEC 61000-4-11 Voltage Dips
and Interrupts
AC Power Ports 30% for 1 period
60% for 50 periods
Signal ports
DC Power Ports
IEC 61000-4-12 Damped Oscillatory
AC Power Ports
2.5 kV common, 1 kV dif-
ferential mode @1 MHz
3
Signal portsIEC 61000-4-16 Mains Frequen-
cy Voltage
DC Power Ports
30 V Continuous
300 V for 1 s
4
IEC 61000-4-17 Ripple on DC
Power Supply
DC Power Ports 10% 3
RUGGEDCOM RX1501
Installation Manual, 05/2020, C79000-G8976-1054-17
55