The following types of protection are possible:
nA
IECEx classification: Ex nA IIC T4 Gc
Certificate no.: DEK 14.0025X
The products meet the requirements of the following standards:
IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
nA [op is]
IECEx classification: Ex nA [op is Gb] IIC T4 Gc
Certificate no.: DEK 14.0026X
The products meet the requirements of the following standards:
IEC 60079-28 (Explosive atmospheres - Part 28: Protection of equipment and
transmission systems using with optical radiation)
IEC 60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of
protection "n")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
ec
IECEx classification: Ex ec IIC T4 Gc
Certificate no.: DEK 18.0017X
The products meet the requirements of the following standards:
IEC 60079-7 (Explosive atmospheres - Part 7: Equipment protection through increased
safety "e")
IEC 60079-0 (Explosive atmospheres - Part 0: Equipment - General requirements)
You will find the current versions of the standards in the currently valid IECEx certificates.
Note for devices with CLASS 1 LASER
Important note on products certified according to Type Examination Certificate KEMA
07ATEX0145 X as of Issue 95 / DEKRA 18ATEX0025X and IECEx Certificate of Conformity
DEK 14.0025X as of Issue 43 / DEK 18.0017X and containing Class 1 optical radiation sources.
Note
CLASS 1 LASER
The device contains optical radiation sources which comply with the limits of Class 1 according
to IEC 60825-1. Fiber-optic cables connected to these optical radiation sources may therefore
be routed either to or through hazardous areas requiring Category 2G, 3G, 2D or 3D
equipment.
EMC directive (electromagnetic compatibility)
The SIMATIC NET products described in these operating instructions meet the requirements
of EU directive 2014/30/EU "Electromagnetic Compatibility" (EMC Directive).
Approvals
SCALANCE XB-200
72 Operating Instructions, 03/2020, C79000-G8976-C359-09

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC NET SCALANCE XB-205-3LD and is the answer not in the manual?

Siemens SIMATIC NET SCALANCE XB-205-3LD Specifications

General IconGeneral
BrandSiemens
ModelSIMATIC NET SCALANCE XB-205-3LD
CategorySwitch
LanguageEnglish

Related product manuals