2 Engineering
Securely Connecting RTU3041C to TeleControl Server Basic
Entry ID: 109739240, V3.0, 07/2021
65
© Siemens AG
2021 All rights reserved
2.2.3 Configuring the TeleControl Server Basic
Note
To make the TeleControl Server Basic accessible via the LAN interface of the
SINEMA Remote Connect Server, store the local IP address of the SINEMA
Remote Connect Server in your PG/PC "TCSB" as the default gateway
(192.168.2.10).
If you have configured several interface cards on your PC or server (e.g., PG/PC
"TCSB"), and you cannot configure a default gateway for the TCSB, add a static
route to the Windows routing table.
1. Start Command Prompt (Desktop app) as administrator.
2. For example, enter the following command:
Route add 172.30.0.0 MASK 255.255.0.0 192.168.2.10
3. Press enter.
Result:
172.30.0.0: Target subnet (VPNs defined IP range)
192.168.2.10: SINEMA RC Server (LAN)
To configure the TeleControl Server Basic, proceed as follows:
1. Open the program "CMT - Configuration and Monitoring Tool" on your PG/PC.
TeleControl Server Basic must be installed on the PG/PC.
2. Log in with your user data.
The following user data is preset at the factory:
User: administrator
Password: 0000
3. When you log in for the first time, assign your own password.