2 PROFINET IO in SIPROTEC
2.4 IO Modules
36 SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
IO Module Single Commands 08
IO Module Single Commands 16
IO Module Double Commands 04
Single commands 08
Category in the hardware catalog Output data
Data type 8 single commands; see Chapter 2.3.2
Data size 2 bytes
Acyclic reading/writing of data None
Parameters None
Single commands 16
Category in the hardware catalog Output data
Data type 16 single commands; see Chapter 2.3.2
Data size 4 bytes
Acyclic reading/writing of data None
Parameters None
Double commands 04
Category in the hardware catalog Output data
Data type 4 double commands; see Chapter 2.3.3
Data size 1 byte
Acyclic reading/writing of data None
Parameters None
com_profinet-io_profile_us.book Page 36 Friday, August 17, 2012 1:40 PM