3 Parameterization
3.4 DCP - Discovery and Basic Configuration Protocol
81SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
3.4 DCP Discovery and Basic Configuration Protocol
3.4.1 Network Settings and Device Name
The network settings of the EN100 and the name of the PROFINET IO device can be changed using DCP
(Discovery and Basic Configuration Protocol). Use the Primary Setup Tool stated in Figure 3-30 for this
purpose.
Access via DCP is also possible if no valid EN100 configuration exists for PROFINET IO.
Figure 3-30 Primary Setup Tool: Main Window
NOTE
A change to the network settings via DCP affects all IP applications running on the EN100, for example HTTP
server and IEC 61850 server. See also Chapter 3.1 and Chapter 3.4.1.
If you change the network settings for a device via DCP, it is no longer possible to access this device via
Ethernet using DIGSI. Accessing the device again from DIGSI via Ethernet requires the network settings stored
for the device to be identical with those stored on the EN100 modules.
com_profinet-io_profile_us.book Page 81 Friday, August 17, 2012 1:40 PM

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC PROFINET IO and is the answer not in the manual?

Siemens SIPROTEC PROFINET IO Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC PROFINET IO
CategoryControl Unit
LanguageEnglish

Related product manuals