Installation Instructions
Document No. 540-149
September 2, 2008
TALON™ Digital Room Temperature
Sensors
Page 1 of 4
Product Description
These sensors allow users to view and adjust points
in the controller using the sensor buttons and digital
display.
These sensors work with Siemens controllers, and
use a 10K Ω thermistor to detect temperature. The
effective sensing and set point range is 55 to 95°F
(13 to 35°C).
The 587-612B includes an integral fan speed switch
that allows users to override the ventilation fan.
These sensors can be mounted on electrical boxes,
stud-type mounting brackets, or drywall. Obtain the
necessary mounting hardware and follow the
appropriate mounting procedures for the type of
installation required.
Product Numbers
587-610B BACnet Digital Room Temperature
Sensor - white
587-612B BACnet Digital Room Temperature
Sensor with fan switch - white
Warning/Caution Notations
CAUTION
Equipment damage, or loss of
data may occur if you do not
follow a procedure as
specified.
Required Tools
• Phillips sizes 1 and 2 screwdrivers
• Medium, flat-blade screwdriver
• Small, flat-blade screwdriver
• Medium-duty electric drill
• 3/16-inch (4.8 mm) drill bit
• 1-inch (25 mm) hole saw
• Small level
• Tape measure
• Marker or pencil
Item Number 540-149, Rev BA
If using non-terminated or damaged cables, you also
need:
• Room sensor connector tool (RJ-11
crimping tool)
• Room sensor connector kit
Expected Installation Time
20 minutes
Prerequisites
• Review these instructions before beginning.
• Installed: appropriate field wiring (standard
six-conductor room sensor cables, plenum),
within the maximum wiring run length for the
individual equipment controller. The
maximum recommended length is 100 feet
(30 m).
• All wiring must comply with National Electric
Code (NEC) and local regulations.
Figure 1. Room Temperature Sensor with Fan Speed.