✓✓✓30-600 Amps
✓✓800 and 1200 Amps
✓✓✓240 Volts AC
✓✓600 Volts AC
✓✓✓250 Volts DC
✓ 600 Volts DC
✓✓✓Double-break visible blade
design (30-200A)
✓✓✓
Quick-make, quick-break switching action
✓✓✓Highly visible ON/OFF handle indication
✓ Handle design for hook stick operation
✓✓✓Padlockable cover latch
✓✓✓Padlockable handle
✓
➂
✓ Single voidable cover interlock
✓✓Dual voidable cover interlock
✓✓✓Type 1 enclosure
✓✓✓Type 3R enclosure
✓✓Type 12 enclosure
✓✓Type 4/4X enclosure
✓✓✓
Generous wiring gutters that meet UL and
NEC wire-bending space requirements
✓✓✓Lugs suitable for copper or aluminum
at 60˚C or 75˚C
✓✓✓CU/AL wire lugs that meet
UL 486B requirements
✓✓Suitable for field-convertible
compression connectors
➅ ✓✓All plated copper current carrying parts
(except lugs)
✓✓✓Spring reinforced Fuse Clips
(except 30A general duty)
✓✓Clear pivoting line terminal shield
✓✓✓Replacement parts
✓ Field addable 200% neutral
✓
➆
✓
➆
✓
➀
Provisions for UL Class T, R and H fuses
✓✓
➀
Provisions for UL Class J and L fuses
✓✓Metal nameplate
✓✓Aux. switch kit
➃ Type 4X with stainless steel interior parts
✓
➄
✓ Rolled flange enclosure design (30-200A)
✓ UL approved HP ratings for
✓ high efficiency motors
✓✓Isolated ground kits
Underwriters’ Laboratories Inc.
Listed by UL under file #E4776 as
enclosed switches and also suitable for
use as service equipment except on
1200A switches on Y systems of more
than 150V to ground.
Meets UL98 standard for enclosed
switches and enclosures
Type 1 switches—general purpose enclo-
sures (Type 1)
Type 3R switches—rainproof enclosures
(Type 3R)
Type 4/4X switches—special purpose
enclosures (Type 4/4X)
Type 12 switches—special
purpose enclosures (Type 12).
Groundable Neutrals
General & Heavy Duty Switches
Switches designed for use on systems
requiring neutrals to have groundable
neutral blocks.
Feature Comparison
General Heavy Double
Duty Duty Throw Features / Ratings
5
➀ 400 & 600A fusible, double-throw switches accept only Class J or T fuses.
➁ 30A general duty switches have fuse clips constructed of spring type copper.
➂ Not supplied on 30A outdoor & plug fuse switches.
➃ 30-200A Type VBII in stainless steel enclosures.
➄ 60-200A
➅ 200A general duty switches have aluminum neutral assemblies.
➆ 100-600A GD and 100-1200A HD switches will accept Class T fuses