Technical Specifications - Three Phase Inverters
(Europe &APAC)
SE4K - SE12.5K
SE4K SE5K SE7K SE8K SE9K SE10K SE12.5K Unit
Output
Rated AC power
output
4000
(1)
5000 7000 8000 9000 10000 12500 VA
Maximum AC power
output
4000 5000 7000 8000 9000 10000 12500 VA
AC output voltage –
line to line / line to
neutral (nominal)
380/ 220; 400/ 230 Vac
AC output voltage
range
184 – 264.5 Vac
AC frequency 50/60 ± 5 Hz
Maximum
continuous output
current (per phase)
6.5 8 11.5 13 14.5 16 20 A
Maximum
continuous
overcurrent
protection
6.5 8 11.5 13 14.5 16 20 A
Residual current
detector / Residual
Current step detector
300 / 30 mA
Grid supported –
three phase
3 / N / PE (WYE with Neutral)
Inrush current AC
(Peak/Duration)
3/ 20
Aac
(rms)
/ ms
Maximum output
fault current
33 A
Power factor range 1 (adjustable from -0.9 to +0.9)
Total harmonic
distortion
< 3%
(1)
SE4K model is available in some countries; refer to the Certifications category in
http://www.solaredge.com/groups/support/downloads
Technical Specifications - Three Phase Inverters (Europe &APAC) 105
Three Phase System Installation Guide MAN-01-00057-4.1