Menulevel1Menulevel2Menulevel3Explanation
Functions
→Analoginput
Analogoutput
Digitalinput
Analoginput
1:SS20.0
2:ETS20.0
3:Notused
3:EHS20.0
4:OT/FPS20.0
5:OS10.5
Showsanalogueinputsfromactive
temperaturesensors.
SS:Supplyairtempsensor.
ETS:Extractairtempsensor.
Notused(VCunits)
EHS:Exhaustairtempsensor(VR
units)
OT/FPS:Overheatprotection
sensor/Frostprotectionsensor.
OS:Outdoorairtempsensor.
Functions
Analoginput
→Analogoutput
Digitalinput
Analogoutput
AO1auto/man/off
0.0V
AO2auto/man/off
7.3V
AO3auto/man10V
Showscurrentanalogueoutputsin0–10Vto
hot/coldwateractuatorandbypassdamper.
SetAO1(Analogueoutputtohotwater
actuator)toauto,manoroff.Defaultis
off.
AO2(Analogueoutputtocoldwateractuator)
toauto,manoroff.Defaultisoff.
AO3(Analogueoutputtobypassdamper)to
autoorman.Defaultisauto.(VCunits)
Selectingmanenablestheusertomanually
controltheactuator/damperwitha0–10V
signal.0Vmeanscompletelyclosedand
10Vcompletelyopenedactuator/bypass
damper.Whenusedonthebypassdamper
theunitcanbeforcedtogotosummer
operationorforceddefrosting(10V).
Functions
→Digitalinput
ConfigDI1–3
ConfigDI4–7
Digitalinput
DI1ON/OFF
DI2ON/OFF
DI3ON/OFF
DI4ON/OFF
DI5ON/OFF
DI6ON/OFF
DI7ON/OFF
Showscurrentsettingofthedigitalinputs
ONorOFF
DI1:Fanconguration
DI2:Fanconguration
DI3:Fanconguration
DI4:Heaterstopped
DI5:Extended/forcedrunning
DI6:Dampertest
DI7:Home/leave
Functions
Digitalinput
→ConfigDI1–3
ConfigDI4–7
ConfigDI1–3
1SFhighEFnom
2SFoffEFlow
3SFhighEFhigh
Usethisdialogueframetosethowyouwant
thefanstoreactto3differentdigitalinputs
whentheyareswitchedonoroff(thesettings
inthecolumntotheleftareexamples).
On/offswitchesneedtobeconnected
physicallytoterminalsonthemainprintcard
toobtainthedifferentfunctions.Seethe
wiringdiagramformoreinformation.
Setthesupplyairfan(SF)andextractair
fan(EF)tooff,low,nomorHighfordigital
inputs1–3
CDControlpanel
ServiceMenu
D2074870
5
SystemairAB