Menulevel1Menulevel2Menulevel3Explanation
Functions
Digitalinput
ConfigDI1–3
ConfigDI4–7
DI4–7
DI4:Stopheat
DI5:Extrun
DI6:Dampertest
DI7:Home/leave
DI4–7aredefaultsetfromfactoryandcan’t
bechangedbytheuser.Belowfollowsa
shortdescriptionofeachfunction.
DI4:Makesitpossibletoturntheelectrical
re-heaterbatteryonoroff.
DI5:TurntheExtended/forcedrunning
functiononoroffbythehelpofaswitch.The
functionoverridescurrentsetfanspeed.
DI6:Automatictestofthebypassdamper
function.Thisdigitalinputisnotavailablefor
theuser.(VCunits).
DI7:Switchingonthisinputdecreases
thesupplyairtempsetpointwith10K.
Thisfunctionisusedwhenthebuildingis
uninhabitedforalongerperiod.
Note:
The“Home/leave”functionisnotworkingif
Waterheaterisactivated.
Functions
Digitaloutput
Defrosting
Modbus
Digitaloutput
1:SF67%
2:EF67%
3:Rotormotor
4:AlarmY/N
5:DmpOFF
6:ReheaterY/N
ShowsThecurrentsettingsofdigitaloutputs
1–5(thesettingsinthecolumntotheleftare
examples).
1:SF67%:Currentsetspeedofthe
supplyairfan(shownaspercentageofthe
maximumspeed).
2:EF67%Currentsetspeedofthe
extractairfan(shownaspercentageofthe
maximumspeed).
3:RotorON/OFF:Indicatediftherotor
isactiveornot(VRunits).
3:Notused(VCunits)
4:AlarmY/N:Indicatesifthesum.
alarmisactiveornot
5:DmpOFF:Outdoor/exhaustairdamper
isonoroff(230Vsignalrelay).
6:ReheaterY/N:Indicatesifthe
electricalre-heaterisactiveornot.
Defrosting
Mode0–5
Usethisdialogueframetosethow
aggressiveyouwantthedefrostingfunction
tooperate.
SetVRunits,defrostingmodebetween0–5,
VCunitsbetween1–5.ForVRdefaultis0,
defaultforVCis3.
Functions
Digitaloutput
Defrosting
Modbus
Allowunbalance
Yes/No
Reducedflow
Active
Bypassdefrosting
Active
Stopdefrosting
Active
OnlyforVCunits.
SetIfyouduringthedefrostingcyclecan
acceptatemporaryunbalanceoftheair
owfromtheunit,i.e.supplyairdecreases.
SelectYESorNO.
Showsifanydefrostingcycleisactive.
Functions
Defrosting
Modbus
Factoryreset
Modbus
Address:1–247
Baud:9600/19200
Parity:
None/Even/Odd
InformationaboutModbuscommunication
andvariablescanbefoundintheModbus
usermanualforresidentialunitsintheonline
catalogueatwww.systemair.com.
CDControlpanel
ServiceMenu
D2074870
6
SystemairAB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SystemAir CD Control Panel and is the answer not in the manual?

SystemAir CD Control Panel Specifications

General IconGeneral
BrandSystemAir
ModelCD Control Panel
CategoryControl Panel
LanguageEnglish

Related product manuals